User Manual
Table Of Contents
- 1 Cyber security disclaimer
- 2 Preconditions of this document
- 3 System overview
- 4 Desigo workflow, tools and programming
- 4.1 Coverage of the technical process
- 4.2 Coverage of the system
- 4.3 Main tasks
- 4.4 Tools for different roles
- 4.5 Working with libraries
- 4.6 Working in parallel and subcontracting
- 4.7 Workflow for primary systems
- 4.8 Workflow for room automation classic
- 4.9 Workflow for Desigo room automation
- 4.10 Desigo Configuration Module (DCM)
- 4.11 Desigo Xworks Plus (XWP)
- 4.12 Desigo Automation Building Tool (ABT)
- 4.13 Programming in D-MAP
- 5 Control concept
- 6 Technical view
- 7 Global objects and functions
- 8 Events and COV reporting
- 9 Alarm management
- 9.1 Alarm sources
- 9.2 Alarm example
- 9.3 Effects of BACnet properties on alarm response
- 9.4 Alarm response of the function blocks
- 9.5 Alarm functions
- 9.6 Alarm management by notification class
- 9.7 Alarm routing over the network
- 9.8 Alarm queuing
- 9.9 Common alarms
- 9.10 Alarm suppression
- 9.11 Alarm message texts
- 10 Calendars and schedulers
- 11 Trending
- 12 Reports
- 13 Data storage
- 14 Network architecture
- 15 Remote access
- 16 Management platform
- 17 Desigo Control Point
- 18 Automation stations
- 19 Logical I/O blocks
- 20 Room automation
- 21 Desigo Open
- 22 System configuration
- 22.1 Technical limits and limit values
- 22.2 Maximum number of elements in a network area
- 22.3 Desigo room automation system function group limits
- 22.4 Devices
- 22.4.1 PXC..D automation stations / system controllers
- 22.4.2 LonWorks system controllers
- 22.4.3 Automation stations with LonWorks integration
- 22.4.4 PX Open integration (PXC001.D/-E.D)
- 22.4.5 PX Open integration (PXC001.D/-E.D + PXA40-RS1)
- 22.4.6 PX Open integration (PXC001.D/-E.D + PXA40-RS2)
- 22.4.7 PX KNX integration (PXC001.D/-E.D)
- 22.4.8 TX Open integration (TXI1/2/2-S.OPEN)
- 22.4.9 Number of data points on Desigo room automation stations
- 22.4.10 Number of data points for PXC3
- 22.4.11 Number of data points for DXR1
- 22.4.12 Number of data points for DXR2
- 22.4.13 PXM20 operator unit
- 22.4.14 PXM10 operator unit
- 22.4.15 Desigo Control Point
- 22.4.16 PXG3.L and PXG3.M BACnet routers
- 22.4.17 SX OPC
- 22.4.18 Desigo CC
- 22.4.19 Desigo Insight
- 22.4.20 Desigo Xworks Plus (XWP)
- 22.4.21 Desigo Automation Building Tool (ABT)
- 22.5 Applications
- 23 Compatibility
- 23.1 Desigo version compatibility definition
- 23.2 Desigo system compatibility basics
- 23.2.1 Compatibility with BACnet standard
- 23.2.2 Compatibility with operating systems
- 23.2.3 Compatibility with SQL servers
- 23.2.4 Compatibility with Microsoft Office
- 23.2.5 Compatibility with web browsers
- 23.2.6 Compatibility with ABT Go
- 23.2.7 Compatibility with VMware (virtual infrastructure)
- 23.2.8 Compatibility of software/libraries on the same PC
- 23.2.9 Hardware and firmware compatibility
- 23.2.10 Backward compatibility
- 23.2.11 Engineering compatibility
- 23.2.12 Compatibility with Desigo Configuration Module (DCM)
- 23.2.13 Compatibility with Desigo PX / Desigo room automation
- 23.2.14 Compatibility with Desigo RX tool
- 23.2.15 Compatibility with TX-I/O
- 23.2.16 Compatibility with TX Open
- 23.3 Desigo Control Point
- 23.4 Upgrading from Desigo V6.2 Update (or Update 2) to V6.2 Update 3
- 23.5 Siemens WEoF clients
- 23.6 Migration compatibility
- 23.7 Hardware requirements of Desigo software products
- 24 Desigo PXC4 and PXC5
- 25 Compatibility of Desigo V6.2 Update 3 with PXC4 and PXC5
Logical I/O blocks
General functions
19
CM110664en_07 241 | 351
Prio Meaning Use Access via
5
immediately to the [PrVal] output. It is
not subject to the delay times defined
for priority 6.
Higher-level monitoring of critical plant
states:
- Frost in ventilation system (close
dampers, stop fans, switch pump on and
open valve)
BACnet command system.
Access via the CMD_CTL block.
6 Minimum switch-on/off time
Prevent unnecessary switching operations.
Switch-on/off delay
Can be used to ensure that run-on delay times are implemented.
No access!
Commands are only generated internally
in the block.
The timer periods [TiOnMin],
[TiOffMin], [DlyOn] and [DlyOff] can be
configured in blocks BO, MO, BVAL and
MVAL.
7 Operating value
Reserved for manual operation.
Local manual operation, e.g.:
- Manual switch
- Mode selector switch
Data flow interconnection via pins:
[ValSwi] und [EnSwi].
8 Higher-level manual operation, e.g.:
- Desigo CC
- Operating unit
- Web client
BACnet command system. Access via:
- Desigo CC
- Operating unit
- Web client
9...13 Not used in Desigo.
14 Program value
Reserved for normal plant operation
with monitoring and control.
Superposed control and monitoring of
the plant.
BACnet command system. Access is via
blocks:
- CMD_CTL
- PWR_CTL (if control enable signal =
Fixed)
15 Local control of plant. Data flow interconnection via pins:
[ValPgm] and [EnPgm].
If the program value is a controller
variable, then [EnPgm] = True and
[ValPgm] = controller variable.
If the program value is not a controller
variable, then [EnPgm] = False.
16 Program value
Reserved for general cross-PX
commands via BACnet references.
BACnet command system. Access via
blocks:
CMD_CTL
PWR_CTL (if control enable signal is =
Released)
Cross-PX via various blocks, e.g.,
ASCHED, BSCHED, MSCHED (name
reference list).
17 Default value [DefVal]
If none of priorities 1…16 is active, then
the default value [DefVal] is processed
instead.
The influence of [DefVal] depends on
the state of the block concerned:
Out-of-service [OoServ=False]:
[DefVal], like the values of priorities
7…16, is subject to the delay times of
priority 6.
[OoServ=True]:
[DefVal] is transmitted immediately to
the [PrVal] output.
BACnet command system. Access via:
- CFC
- PXM20
- Web client
Example: Effect of priorities 7...16 on [PrVal]