Automation stations
Operating states
18
232 | 351 CM110664en_07
STOP
: The D-MAP program is stopped.
RUN
: The D-MAP program runs.
KOMA
: The automation station is in a prolonged sleep mode.
The following figure shows the operating states and the associated transitions:
Operating states
Mains off
No power supply
STOP
I/O scan active
Ready for wiring test (only possible without D-MAP program loaded) (PXM20, for PTM modules only)
D-MAP program processing stopped
Communication with XWP: Master reset, complete loading and delta loading allowed
BACnet communication with Desigo CC and PXM20: ReadProperty, WriteProperty, Who-Has, COVs,
EventNotification, AcknowledgeAlarm GetEventInformation
COVs: For values changed by the operator, values cannot be changed by the program
Alarming: Alarm monitoring inactive, no new alarms or events are generated (the device info object can
still generate alarms and system events). Notification of saved alarms and events is possible if recipient
lists are set up. GetEventInformation and AcknowledgeAlarm possible.
Primary server in the STOP state: Primary server is not active, that is, no life check, no time
synchronization and no replication of global objects
Backup server in the STOP state: The backup server is not active, that is, no time synchronization and
no replication of global objects by primary server. The backup server will not accept changes to global
objects by a client.
RUN
I/O scan active
Wiring test not allowed
D-MAP program processing active
Communication with XWP: Master reset and complete loading not allowed, delta loading allowed
STOP
Mains OFF
BACnet: Download
required
COMA
RUN
BACnet: Operational
BACnet: Operational
15: Delta loading
16: Delta loading
7: Restart 9: Reset
4: RUN Cmd
5: STOP Cmd
7: Restart 9: Reset
14: Load
13: Master reset
10: Fatal Error
12: Reanimation
11: Fatal Error
1: Power failure 2: Power restored STOP
1: Power failure
2: Power restored RUN
1: Power failure
2: Power restored COMA