Values read in cycle 1 are processed in cycle 2. Output values calculated in cycle 1 are transferred to the
peripherals in cycle 2.
18.1 Device object
Each automation station contains a device object. The device object:
Contains the device and system information for the automation station
Is based on the standard BACnet object as defined in the BACnet standard, and contains additional
proprietary properties
Is always present and is set up in the automation station with initial values
Is not programmed in the CFC Editor as a function block and is not loaded with the program
You can monitor property values through a BACnet client (e.g., Desigo CC, XWP). You can change default
values. You cannot read changed values back into Xworks Plus (XWP). When an automation station is
replaced, you must reenter any changes made to property values.
Process image
buffer
Read Write
I/O scan
AI AO
Frozen values
Current values