- 5 Control concept
- 6 Technical view
- 7 Global objects and functions
- 8 Events and COV reporting
- 9 Alarm management
- 9.1 Alarm sources
- 9.2 Alarm example
- 9.3 Effects of BACnet properties on alarm response
- 9.4 Alarm response of the function blocks
- 9.5 Alarm functions
- 9.6 Alarm management by notification class
- 9.7 Alarm routing over the network
- 9.8 Alarm queuing
- 9.9 Common alarms
- 9.10 Alarm suppression
- 9.11 Alarm message texts
- 10 Calendars and schedulers
- 11 Trending
- 12 Reports
- 13 Data storage
- 14 Network architecture
- 15 Remote access
- 16 Management platform
- 17 Desigo Control Point
- 18 Automation stations
- 19 Logical I/O blocks
- 20 Room automation
- 21 Desigo Open
- 22 System configuration
- 22.1 Technical limits and limit values
- 22.2 Maximum number of elements in a network area
- 22.3 Desigo room automation system function group limits
- 22.4 Devices
- 22.4.1 PXC..D automation stations / system controllers
- 22.4.2 LonWorks system controllers
- 22.4.3 Automation stations with LonWorks integration
- 22.4.4 PX Open integration (PXC001.D/-E.D)
- 22.4.5 PX Open integration (PXC001.D/-E.D + PXA40-RS1)
- 22.4.6 PX Open integration (PXC001.D/-E.D + PXA40-RS2)
- 22.4.7 PX KNX integration (PXC001.D/-E.D)
- 22.4.8 TX Open integration (TXI1/2/2-S.OPEN)
- 22.4.9 Number of data points on Desigo room automation stations
- 22.4.10 Number of data points for PXC3
- 22.4.11 Number of data points for DXR1
- 22.4.12 Number of data points for DXR2
- 22.4.13 PXM20 operator unit
- 22.4.14 PXM10 operator unit
- 22.4.15 Desigo Control Point
- 22.4.16 PXG3.L and PXG3.M BACnet routers
- 22.4.17 SX OPC
- 22.4.18 Desigo CC
- 22.4.19 Desigo Insight
- 22.4.20 Desigo Xworks Plus (XWP)
- 22.4.21 Desigo Automation Building Tool (ABT)
- 22.5 Applications
- 23 Compatibility
- 23.1 Desigo version compatibility definition
- 23.2 Desigo system compatibility basics
- 23.2.1 Compatibility with BACnet standard
- 23.2.2 Compatibility with operating systems
- 23.2.3 Compatibility with SQL servers
- 23.2.4 Compatibility with Microsoft Office
- 23.2.5 Compatibility with web browsers
- 23.2.6 Compatibility with ABT Go
- 23.2.7 Compatibility with VMware (virtual infrastructure)
- 23.2.8 Compatibility of software/libraries on the same PC
- 23.2.9 Hardware and firmware compatibility
- 23.2.10 Backward compatibility
- 23.2.11 Engineering compatibility
- 23.2.12 Compatibility with Desigo Configuration Module (DCM)
- 23.2.13 Compatibility with Desigo PX / Desigo room automation
- 23.2.14 Compatibility with Desigo RX tool
- 23.2.15 Compatibility with TX-I/O
- 23.2.16 Compatibility with TX Open
- 23.3 Desigo Control Point
- 23.4 Upgrading from Desigo V6.2 Update (or Update 2) to V6.2 Update 3
- 23.5 Siemens WEoF clients
- 23.6 Migration compatibility
- 23.7 Hardware requirements of Desigo software products
- 24 Desigo PXC4 and PXC5
- 25 Compatibility of Desigo V6.2 Update 3 with PXC4 and PXC5
Alarm management
Alarm management by notification class
9
156 | 351 CM110664en_07
Each alarm-generating object is assigned one notification class [NotifCl] only, but one notification class
can be used by more than one alarm-generating object. This makes it possible to create a Notification
Class object for each group of alarms (e.g., HVAC alarms, fire alarms etc.). Each alarm source in a given
alarm group is assigned to the [NotifCl] for that group.
There are global and local notification class objects:
● Global notification class: One set of max. 18 global notification class objects per site. Global notification
classes are replicated and thus exist on all Desigo PX of a site in identical form.
● Local notification class: On Desigo PX, local notification classes can be engineered, but are NOT
replicated.
● Desigo room automation supports exclusively local notification classes.
Interface definition
The notification class function block [NotifCl] is the means by which functionality is transferred from the
BACnet standard into the CFC environment.
This function block contains the instance number of the Notification Class (an integer). which must be
identical to the value entered in the subordinate alarm sources. This makes it possible to create a unique
reference.
The number must not be modified online.
Notification class number
There are 18 predefined global notification classes. The notification class is identified with the two
independent variables AlarmFunction and AlarmClass, and referenced in the alarm source:
● AlarmFunction [Simple(1), Basic(2), Extended Alarm(3)]
● AlarmClass [UrgentAlarm (1), HighPrioAlarm (2), NormalAlarm (3), LowPrioAlarm (4),
UserDefinedAlarm (5) and OffLineTrend (6)]
Formula
The notification class number is calculated as follows:
NotificationClass# := 10 * AlarmClass + AlarmFunction
This gives the following notification classes:
AlarmClass AlarmFunction Priority
(default values)
To-Offnormal
To-Fault
To-Normal
Uses NotificationClass#
(derived)
Highly critical alarms,
system messages, device
info object
UrgentAlarm Simple 1, 1, 5 11
UrgentAlarm Basic 1, 1, 5 12