User Manual
Table Of Contents
- 1 Cyber security disclaimer
- 2 Preconditions of this document
- 3 System overview
- 4 Desigo workflow, tools and programming
- 4.1 Coverage of the technical process
- 4.2 Coverage of the system
- 4.3 Main tasks
- 4.4 Tools for different roles
- 4.5 Working with libraries
- 4.6 Working in parallel and subcontracting
- 4.7 Workflow for primary systems
- 4.8 Workflow for room automation classic
- 4.9 Workflow for Desigo room automation
- 4.10 Desigo Configuration Module (DCM)
- 4.11 Desigo Xworks Plus (XWP)
- 4.12 Desigo Automation Building Tool (ABT)
- 4.13 Programming in D-MAP
- 5 Control concept
- 6 Technical view
- 7 Global objects and functions
- 8 Events and COV reporting
- 9 Alarm management
- 9.1 Alarm sources
- 9.2 Alarm example
- 9.3 Effects of BACnet properties on alarm response
- 9.4 Alarm response of the function blocks
- 9.5 Alarm functions
- 9.6 Alarm management by notification class
- 9.7 Alarm routing over the network
- 9.8 Alarm queuing
- 9.9 Common alarms
- 9.10 Alarm suppression
- 9.11 Alarm message texts
- 10 Calendars and schedulers
- 11 Trending
- 12 Reports
- 13 Data storage
- 14 Network architecture
- 15 Remote access
- 16 Management platform
- 17 Desigo Control Point
- 18 Automation stations
- 19 Logical I/O blocks
- 20 Room automation
- 21 Desigo Open
- 22 System configuration
- 22.1 Technical limits and limit values
- 22.2 Maximum number of elements in a network area
- 22.3 Desigo room automation system function group limits
- 22.4 Devices
- 22.4.1 PXC..D automation stations / system controllers
- 22.4.2 LonWorks system controllers
- 22.4.3 Automation stations with LonWorks integration
- 22.4.4 PX Open integration (PXC001.D/-E.D)
- 22.4.5 PX Open integration (PXC001.D/-E.D + PXA40-RS1)
- 22.4.6 PX Open integration (PXC001.D/-E.D + PXA40-RS2)
- 22.4.7 PX KNX integration (PXC001.D/-E.D)
- 22.4.8 TX Open integration (TXI1/2/2-S.OPEN)
- 22.4.9 Number of data points on Desigo room automation stations
- 22.4.10 Number of data points for PXC3
- 22.4.11 Number of data points for DXR1
- 22.4.12 Number of data points for DXR2
- 22.4.13 PXM20 operator unit
- 22.4.14 PXM10 operator unit
- 22.4.15 Desigo Control Point
- 22.4.16 PXG3.L and PXG3.M BACnet routers
- 22.4.17 SX OPC
- 22.4.18 Desigo CC
- 22.4.19 Desigo Insight
- 22.4.20 Desigo Xworks Plus (XWP)
- 22.4.21 Desigo Automation Building Tool (ABT)
- 22.5 Applications
- 23 Compatibility
- 23.1 Desigo version compatibility definition
- 23.2 Desigo system compatibility basics
- 23.2.1 Compatibility with BACnet standard
- 23.2.2 Compatibility with operating systems
- 23.2.3 Compatibility with SQL servers
- 23.2.4 Compatibility with Microsoft Office
- 23.2.5 Compatibility with web browsers
- 23.2.6 Compatibility with ABT Go
- 23.2.7 Compatibility with VMware (virtual infrastructure)
- 23.2.8 Compatibility of software/libraries on the same PC
- 23.2.9 Hardware and firmware compatibility
- 23.2.10 Backward compatibility
- 23.2.11 Engineering compatibility
- 23.2.12 Compatibility with Desigo Configuration Module (DCM)
- 23.2.13 Compatibility with Desigo PX / Desigo room automation
- 23.2.14 Compatibility with Desigo RX tool
- 23.2.15 Compatibility with TX-I/O
- 23.2.16 Compatibility with TX Open
- 23.3 Desigo Control Point
- 23.4 Upgrading from Desigo V6.2 Update (or Update 2) to V6.2 Update 3
- 23.5 Siemens WEoF clients
- 23.6 Migration compatibility
- 23.7 Hardware requirements of Desigo software products
- 24 Desigo PXC4 and PXC5
- 25 Compatibility of Desigo V6.2 Update 3 with PXC4 and PXC5
Alarm management
Effects of BACnet properties on alarm response
9
146 | 351 CM110664en_07
blocks (including the BACnet Device Info Object) are only monitored in the operational status RUN.
Corresponds to the standard BACnet Property Out_of_Service.
Present value [PrVal]
OFFNORMAL alarms are monitored exclusively on the basis of the current value of [PrVal] the present
value variable. The source of this present value (whether a process value, operator value, replacement
value or commanded value) is irrelevant. This is equivalent to the standard BACnet property Present_Value.
Reliability [Rlb]
The value under [PrVal] is only plausible if [Rlb] = NO_FAULT_DETECTED.
When [Rlb] <> NO_FAULT_DETECTED, this is precisely the condition for a FAULT alarm.
The BACnet Device Info Object is an exception. The value of [Rlb] for the BACnet device object is
NO_FAULT_DETECTED, except in the case of the fault FLASH_FULL (FAULT condition). This is equivalent
to the standard BACnet property Reliability.
Reference value [RefVal]
[RefVal] is a set point, used to set the value which [PrVal] (the measured value) must assume in order to
initiate an alarm after the time defined by [TiMonDvn] has expired. [RefVal] is equivalent to the standard
BACnet property Alarm_Value.
Reference values [RefVals]
The variable [RefVals] comprises a list of multistate elements. The value range (number of states) of the
items in the list is the same as for [PrVal]. All states to be treated as OFFNORMAL are entered under
[RefVals]. [RefVals] is equivalent to the standard BACnet property Alarm_Values.
Example of [RefVals] : STEP 1, STEP 2, STEP 4
Name Value
State 1 STEP 1
State 2 STEP 2
State 3 STEP 4
In this example, an incoming OFFNORMAL alarm will be detected if [PrVal] = STEP 1, STEP 2 or STEP 4
after expiry of the period defined by [TiMonDvn].
State flag [StaFlg]
The variable [StaFlg] includes the two bits 'In_Alarm' and 'Fault'.
By definition, In_Alarm is TRUE whenever [EvtSta] is not equal to NORMAL.
By definition, FAULT is TRUE whenever [EvtSta = FAULT].
The value of these two [StaFlg] variables is thus derived from another variable.
For each change of the variable [StaFlg] a Change of Value (COV) notification is sent to all COV
subscribers of the alarm-generating object. In this way, the COV subscribers can be kept informed of an
alarm state in their COV server. This is equivalent to the standard BACnet property Status_Flags.
Suppress event detection [SupEvtDet]
[SupEvtDet] (Boolean type) lets you turn the OFFNORMAL and FAULT alarm detection on/off.
OFFNORMAL and FAULT alarms are only detected when [SupEvtDet] = FALSE. This is equivalent to the
standard BACnet property Event_Algorithm_Inhibit.
Event time stamp [TiStmEvt]
This variable (ARRAY [3], type TimeStamp), contains time stamps for the last changes of state of the
alarm-generating object TO_OFFNORMAL, TO_FAULT and TO_NORMAL. The value of the variables is
updated immediately after the associated alarm state transition. This is equivalent to the standard BACnet
property Event_Time_Stamps.
Notification function selector [NotifSel]
This variable specifies if the alarm function is executed as per default pattern (Simple-/Basic-/Extended
alarm) or as per a customized alarm function.