User Manual

System configuration
Devices
22
318 | 351 CM110664en_07
22.4 Devices
22.4.1 PXC..D automation stations / system controllers
PX Compact PX Modular PX Open
10
PX KNX
9
Item PXC12.D
PXC12-E.D
PXC22.D
PXC22-E.D
PXC-NRUF
PXC22.1.D
PXC22.1-
E.D
PXC36.1.D
PXC36.1-
E.D
PXC50.D
PXC50-E.D
PXC100.D
PXC100-E.D
PXC200.D
PXC200-E.D
PXC00.D
PXC00-E.D
PXC001.D
PXC001-E.D
+ PXA40-
RS..
PXC001.D
PXC001-E.D
Temporary
alarm receiver
1
18* 18* 18* 18* 18* 18* 18* 18*
Configured
alarm receivers
2
20* 20* 20* 20* 20* 20* 20* 20*
BACnet
references
COV server
resources
3
[1,400*] [1,400*] [1,400*] [1,400*] [1,400*] [1,400*] [1,400*] [1,400*]
BACnet
references
COV client
resources
4
400* 950* 950* 950* 950* 950* 650* 400*
Total BACnet
objects
[4,000] [4,000] [4,000] [4,000] [4,000] [4,000] [4,000] [4,000]
Number of
function block
instances
(application
size)
1,900* 1,900* 1,900* 1,900* 2,900* 1,900* 2,900* 2,900*
Trend log
5
100 100 100 200 350 200 600 100
Trend log
multiple
19
20 20 20 20 20 20 20 20
Scheduler 15
17
15
17
50
18
50
18
50
18
50
18
50
17
50
17
Calendar
14
10 10 50 50 50 50 50 50
PXM10 1 1 1 1 1 1 1 n/a
PPS2 devices
(ALN)
8
(e.g.
QAX3.x,
RXZ90.1)
5 5 n/a n/a n/a n/a 5 n/a
Physical data
points onboard
12 / 22 / 64 22 / 36 n/a n/a n/a n/a n/a n/a
Physical data
points TX-I/O
n/a 16 52* 200*
15
(350)
15
n/a n/a n/a
Physical data
points TX-I/O +
PTM
n/a n/a 52* 200*
15
(350)
15
n/a n/a n/a
Total number of
data points
onboard + TX-
I/O + PTM +
TX Open
n/a 400* 400* 600*
15
(1,000)
15
n/a n/a n/a
TX Open per
island bus
n/a 5 5 5 5 n/a n/a n/a
PXX-PBUS n/a n/a 1 1 1 n/a n/a n/a