User Manual
Room automation
Desigo room automation
20
294 | 351 CM110664en_07
Room operating • • • •
Heated / Chilled ceiling
radiator
• •
VAV system • • • • •
Central functions
1
Housing
DIN
Flat •
2
•
2
•
2
•
2
•
2
Operating voltage
230V
24V • • • • •
Inputs and outputs onboard
Digital inputs 1 1
Universal inputs 2 2 2 2
Relay outputs
Triac outputs 4 4 4 4
Analog outputs (DC 0...10 V)
3
1 1 1 1
Pressure sensor 1 1 1 1 1
Maximum configuration
Number of I/O data points
4
16 16 22 19 2
Integrated power supply for
KNX (mA)
50 50
Key
1
Cannot be combined with other applications.
2
Mounting via damper shaft.
3
Cannot be extended by KNX PL-Link inputs and outputs.
4
Total number of data point used by TX-I/O, KNX PL-Link and DALI. For details, see chapter
System Configuration
.
Accessories for DXR1 automation stations
Accessory device
QMA1.N30H Room sensor for DXR1 room automation stations
QMX1.M34H Room unit for DXR1 room automation stations
DXA.T50 Air tube accessory kit 50 mm
See
Compact room automation station, BACnet/IP, AC 24 V (Actuating DXR) DXR1.E02PLZ-112
(A6V11393935)