User Manual

Room automation
Desigo room automation
20
CM110664en_07 287 | 351
DALI
DALI (Digital Addressable Lighting Interface) helps control lighting.
20.1.1 Configurable
DXR2.. can automate up to two rooms for heating, ventilation, air conditioning, shading, and lighting,
whereas DXR1 can automate one room and heating, ventilation, and air conditioning only.
The stations communicate with each other and other system components, depending on the type, via
BACnet/IP (DXR1.E../DXR2.E..) or BACnet MS/TP (DXR1.M../DXR2.M..). The room automation stations
have a set number of I/O data points and an onboard interface to KNX to connect field devices. The
automation stations are delivered with preloaded applications and only need to be configured.
A comprehensive library of proven, standardized applications is also available and can be used instead of
the preloaded applications. Buttons, sensors, and actuators for lighting and shading are connected to the
room automation stations via the KNX PL-Link.
The preloaded and proven standardized applications in the library are configured using ABT Site and offer a
great deal of flexibility since the inputs and outputs of the DXR1../DXR2.. can also be configured in addition
to the functions.
See
Desigo Configurable Room Automation (BACnet) – Product Range Description
(A6V10866237).
Compact DXR2 room automation stations for BACnet/IP
°C
°C
°C
°C
BACnet/IP
KNX PL-Link
KNX PL-Link
Ethernet
Desigo CC
Detector
PXC..-E.D
Detector
QMX3...
Room operator units
AQR25..
Room sensor
AQR25..
Room sensor
QMX3...