Logical I/O blocks
Slope [Slpe] and Intercept [Icpt]
19
274 | 351 CM110664en_07
Value (decimal) Text
74 Destination device unknown.
75 Feedback device unknown.
76 Destination object unknown.
77 Feedback object unknown.
78 Unsuitable destination type.
79 Unsuitable feedback type.
80 Unreliable destination object.
81 Unreliable feedback object.
82 Invalid subsystem (syntax error).
83 Invalid feedback subsystem (syntax error).
84 Memory full.
85 Unreliable target device.
86 Communication failure reported in subsystem.
87 Alarm in subsystem application.
88 Maximum BACnet references reached for device.
89 Reliable participant.
90 Feedback error reported in binary output.
91 Invalid reference: Address not valid.
92 Reference object cannot be commanded.
93 Actual operating mode not found in command list.
94 Invalid priority set for command (valid : 2,4,14,16).
95 Invalid object number configured in sequence table.
96 Invalid object type configured in sequence table.
97 Invalid step control configured in sequence table.
98 Neighboring object not reachable.
99 Command lists indicate different variables.
100 Invalid calendar reference.
101 Configured switch kind not supported by destination controller.
102 Multistate mapping error.
19.9 Slope [Slpe] and Intercept [Icpt]
[Slpe] and [Icpt] value exist for:
I/O modules (PX Modular and PX Compact)
These values impact signal type (the I/O module).
Siemens field devices
These values affect the combination of Slpe and Icpt values for the signal type, the field device and its
measurement and positioning range. XWP automatically enters these values, and they can be changed
there, e.g., to consider the line resistance of a sensor or to describe a third-party sensor.
BACnet referencing
PPS2 interface
The combined values [Slpe] and [Icpt] can be calculated as follows from individual values for signal type
(I/O module) and characteristic curve (field device):