User Manual

Logical I/O blocks
General functions
19
240 | 351 CM110664en_07
3. The switch-on or switch-off delay timer starts.
4. After expiry of [TiOnMin] or [TiOffMin], priority 6 is set to inactive.
If the delay times [DlyOn] or [DlyOff] are equal to 0, no action is taken.
If the new value which determines [PrVal] is the same as the current [PrVal], then, here too, no action is
taken.
The minimum on/off time
For each change at the output [PrVal] from OFF to Stage n or from Stage n to OFF, the entry for priority 6 is
set up as follows:
If the minimum ON-time [TiOnMin] or OFF-time [TiOffMin] is greater than 0:
1. Priority 6 adopts the new present value [PrVal].
2. Priority 6 is set to active.
3. The timer for the minimum on-time or off-time is started.
4. After expiry of [TiOnMin] or [TiOffMin], priority 6 is set to inactive.
If the minimum switch-times [TiOnMin] / [TiOffMin] are set to 0, no action is taken.
Constraints
The functions described above are supported only by the BO, MO, BVAL and MVAL blocks.
With multistage switch commands, the monitoring periods are enabled only when switching from OFF
to Stage n or from Stage n to OFF. When switching from one stage to another (e.g., Stage 1 to Stage 2),
the timer times are not enabled.
However, any timer times already running will continue to run.
Application
Unnecessary on/off switching operations can be prevented by activating minimum switch-on or switch-
off times.
Activating switch-on or switch-off delays ensures that run-on time delays are maintained.
Information bit
In order for a given value to be included in the evaluation of [PrioArr], its information bit must be set.
The following applies to priority 1,4,7 and 15 (data flow connection): The relevant information bit is set via
pins [EnSfty], [EnCrit], [EnSwi] and [EnPgm].
The following applies to priority 2, 5, 8, 14 and 16 (BACnet command system): When a given value is
commanded via BACnet, the value concerned is entered in the [PrioArr] and the associated information bit
is set automatically.
The following applies to priority level 6: Both the value and the information bit are handled by the block
concerned.
Prio Meaning Use Access via
1 Safety value (life safety)
Reserved for the initiation of safety
functions (1 = highest priority).
If priority 1 or 2 becomes the
determining value for [PrVal], then the
value concerned is transmitted
immediately to the [PrVal] output. It is
not subject to the delay times defined
for priority 6.
Local safety function, e.g.:
- Fire
- EMERGENCY OFF
- Service switch
- Gas alarm
- Thermal package
Data flow interconnection via pins:
[ValSfty] and [EnSfty].
Normally, [ValSfty] is a constant and
[EnSfty] can be enabled/disabled.
2 Higher-level safety function, e.g.:
- Smoke extraction
BACnet command system.
Access via the CMD_CTL block.
3 Not used in Desigo.
4 Critical value (plant protection)
Reserved for monitoring critical plant
states.
If priority 4 or 5 becomes the
determining value for [PrVal], then the
value concerned is transmitted
Local monitoring of critical plant states,
e.g.:
- Frost protection (protection from
excess cooling)
- Interlock of aggregates
- Icing protection
Data flow interconnection via pins:
[ValCrit] und [EnCrit].
Normally, [ValCrit] is a constant and
[EnCrit] is enabled/disabled.