User Manual

Automation stations
Operating states
18
234 | 351 CM110664en_07
Cold start I/O scan: Default values for output modules
Cold start function block variables: Volatile variables are initialized with initial value. Non-volatile
variables retain their last value.
The STOP state is reached when the I/O scan is finished.
7 Restart
Restart of the automation station due to software error.
Actions (cold start response):
Cold start I/O scan: Default values for output modules
Cold start function block variables: Volatile variables are initialized with initial value. Non-volatile
variables retain their last value.
System event: Restart
D-MAP processing starts when the first I/O scan is finished.
8 Reset
Explicit reset of automation station via hardware push button.
Actions (cold start response):
Cold start I/O scan: Default values for output modules
Cold start function block variables: Volatile variables are initialized with initial value. Non-volatile
variables retain their last value.
The STOP state is reached when the I/O scan is finished.
9 Reset
Explicit reset of automation station via hardware switch.
Actions (cold start response):
Cold start I/O scan: Default values for output modules
Cold start function block variables: Volatile variables are initialized with initial value. Non-volatile
variables retain their last value
System event: Reset
D-MAP processing starts when the first I/O scan is finished.
10, 11 Fatal Error
Restart due to fatal error in the software or in the D-MAP program. Criterion: Same error occurs three
times within 15 minutes.
Actions (cold start response):
Stop I/O scan If possible: Loss of hardware output values for compact and modular automation stations
Stop BACnet communication
Stop XWP communication
D-MAP processing is stopped.
12 Reanimation
Only possible by deleting the D-MAP program (press ForceFWDownload pin and reset the automation
station).
Actions (cold start response):
Change of required operating state to STOP
Cold start I/O scan: Default values for output modules
The STOP state is reached when the I/O scan is finished.
13 Master reset
Deletion of D-MAP program on automation station with XWP.
Cold start I/O scan: Default values for output modules
D-MAP program data including system and event queue is deleted.
14 Load
Complete loading of a new D-MAP program.
Before downloading, a master reset must be carried out.
Function block variables are loaded with initialized values.
15 Delta download
D-MAP program changes are loaded.