User Manual
Automation stations
Operating states
18
CM110664en_07 231 | 351
When a critical hardware or software error occurs, the automation station tries to restart. If the same error
is detected three times within 15 minutes, the automation station switches to the COMA operating state. If
the Fault LED is lit, the automation station is in the COMA operating state.
Online properties for diagnostics
The values in the Online Properties window in Xworks Plus (XWP) give clues about the operation of the
automation station.
18.4 Operating states
A PX automation station has the following operating states: