Triggered Sampling
In Triggered Sampling an application (e.g., via data flow interconnection) determines when values are
acquired/logged and saved. Triggered Sampling is supported by the Trendlog object and the Trendlog
Multiple object.
11.2 Editing parameters
Many of the parameters in the trend log object are definable only if:
● Enable for logging (Enable logging) [EnLog] is
inactive
● The log buffer is
empty
(Record count = 1)
In this state, the following variables can be modified:
– Start time [TiStt] and stop time [TiStp]
– Interval [Ivl]
– Buffer size [BufSize]
– Record count [RecCnt] (can only be overwritten with 0: delete log buffer)
– Notification threshold [NotifThd]
– Input/Output address [IOAddr] (if an unavailable BACnet address is entered, an alarm is initiated)
● [EnLog] is
inactive
or
active
● The log buffer is
not empty
(log count > 1)
In this state, only the following parameters can be configured: