User Manual
Alarm management
Alarm management by notification class
9
158 | 351 CM110664en_07
Operator units:
● Permanently connected operator units (and hence, alarm receivers) are addressed by their Device
Name.
● Operator units (and hence alarm receivers) with a point-to-point connection (PTP connection) are
addressed with a Remote Area Site identifier and their Device Name. For example:
B=fff for permanent connection
B=kkk:aa for point-to-point connection (PTP connection)
● Adjustments are required during the addressing process so that there is no conflict between the names
of operator units and the plant or room management designations.
Permanent and point-to-point connections:
● For alarm receivers, the address syntax (see further below) indicates the type of connection: permanent
or PTP connections.
● Desigo PX automation stations with half-routers must know the Remote Area Site designators of their
remote alarm receivers to enable an PX automation station to resolve the remote alarm receiver
designator.
Remote-Area_Site "Luzern"
Device Name "CC 01"
BACnet PTP
Remote-Area_Site "Bern"
Device Name "CC 02" Device Name "CC 03"
Site "Muri"
Site
"Suhr"
Router
Site
"Emmen"
Site
"Sempach"
Device Name "CC 04"
BACnet PTP