User's Manual
Table Of Contents
- Safety Notes
- FCC Conformity
- CE Electromagnetic Compatibility (EMC) Conformity
- Industry Canada
- The Manual
- Technical Support
- Abbreviations and Identifications
- SITRANS LR560 Overview
- Specifications
- Installation
- Wiring
- Local Operation
- Operating via SIMATIC PDM
- Functions in SIMATIC PDM
- SIMATIC PDM Version
- Quick Start Wizard via SIMATIC PDM
- Changing parameter settings using SIMATIC PDM
- Operating via FDT (Field Device Tool)
- Parameter Reference
- 1. Quick Start
- 2. Setup
- 2.1. Identification
- 2.2. Device
- 2.3. Sensor
- 2.4. Signal Processing
- 2.4.1. Near Range
- 2.4.2. Far Range
- 2.4.3. Minimum Sensor Value
- 2.4.4. Maximum Sensor Value
- 2.4.5. Echo select
- 2.4.6. Sampling
- 2.4.7. Echo Quality
- 2.4.8. TVT setup
- 2.4.9. TVT shaper
- 2.4.9.1. Breakpoint 1-9
- 2.4.9.2. Breakpoint 10-18
- 2.4.9.3. Breakpoint 19-27
- 2.4.9.4. Breakpoint 28-36
- 2.4.9.5. Breakpoint 37-45
- 2.4.9.6. Breakpoint 46-54
- 2.4.9.7. Breakpoint 55-63
- 2.4.9.8. Breakpoint 64-72
- 2.4.9.9. Breakpoint 73-81
- 2.4.9.10. Breakpoint 82-90
- 2.4.9.11. Breakpoint 91-99
- 2.4.9.12. Breakpoint 100-108
- 2.4.9.13. Breakpoint 109-117
- 2.4.9.14. Breakpoint 118-120
- 2.5. AIFB1
- 2.6. AIFB2
- 2.7. Measured Values
- 2.8. Filtering
- 3. Diagnostics
- 4. Service
- 5. Communication
- 6. Security
- 7. Language
- Appendix A: Alphabetical Parameter List
- Appendix B: Troubleshooting
- Appendix C: Maintenance
- Appendix D: Technical Reference
- Principles of Operation
- Echo Processing
- Measurement Response
- Damping
- Loss of Echo (LOE)
- Temperature derating curve
- Appendix E: PROFIBUS PA Profile Structure
- Appendix F: Communications via PROFIBUS PA
- Appendix G: Firmware Revision History
- Glossary
- Index
- LCD menu structure
7ML19985LT01 SITRANS LR560 (PROFIBUS PA) – OPERATING INSTRUCTIONS Page 87
mmmmm
Parameters
4.2. Master Reset
To access via SIMATIC PDM:
Open the menu Device – Master Reset. For more detail see
Master Reset on page 55
.
To perform a reset via the handheld programmer:
a) Press RIGHT Arrow to open Edit Mode then scroll down to the desired Reset
option and press RIGHT Arrow to select it.
b) Press LEFT Arrow to exit.
4.3. Powered Hours
Read only. Displays the number of hours the unit has been powered up since
manufacture.
To view via SIMATIC PDM, open the menu Device – Wear.
Notes:
• Following a reset, some degree of reprogramming may be required, depending
on the option chosen below.
• While performing any reset, a loss of communications can be expected.
Reset Options Result
Factory Defaults
Resets all user parameters to the manufacturer’s default settings,
with certain exceptions. The list of exceptions includes, but is not
limited to:
• Message
•Description
• Installation Data
• Device Address
• Write Protection
• Auto False Echo Suppression Range
• Learned TVT
•Language
Standard
Defaults
Resets all parameters, excluding device addresses and Language, to
the PROFIBUS standard default settings.
NOTE:
After initiating a reset to Standard Defaults via the local
user interface, allow 1-2 minutes before initiating a new
command locally.
Informational Resets parameters such as Tag.
Functional
Resets parameters that control device behavior and functionality
(such as calibration points)
Warm Start Has the same effect as recycling power to the device
Reset Address
to 126
• Resets the PROFIBUS device address to 126
• If the address lock was on, will disable the lock.