User's Manual
Table Of Contents
- Safety Notes
- FCC Conformity
- CE Electromagnetic Compatibility (EMC) Conformity
- Industry Canada
- The Manual
- Technical Support
- Abbreviations and Identifications
- SITRANS LR560 Overview
- Specifications
- Installation
- Wiring
- Local Operation
- Operating via SIMATIC PDM
- Functions in SIMATIC PDM
- SIMATIC PDM Version
- Quick Start Wizard via SIMATIC PDM
- Changing parameter settings using SIMATIC PDM
- Operating via FDT (Field Device Tool)
- Parameter Reference
- 1. Quick Start
- 2. Setup
- 2.1. Identification
- 2.2. Device
- 2.3. Sensor
- 2.4. Signal Processing
- 2.4.1. Near Range
- 2.4.2. Far Range
- 2.4.3. Minimum Sensor Value
- 2.4.4. Maximum Sensor Value
- 2.4.5. Echo select
- 2.4.6. Sampling
- 2.4.7. Echo Quality
- 2.4.8. TVT setup
- 2.4.9. TVT shaper
- 2.4.9.1. Breakpoint 1-9
- 2.4.9.2. Breakpoint 10-18
- 2.4.9.3. Breakpoint 19-27
- 2.4.9.4. Breakpoint 28-36
- 2.4.9.5. Breakpoint 37-45
- 2.4.9.6. Breakpoint 46-54
- 2.4.9.7. Breakpoint 55-63
- 2.4.9.8. Breakpoint 64-72
- 2.4.9.9. Breakpoint 73-81
- 2.4.9.10. Breakpoint 82-90
- 2.4.9.11. Breakpoint 91-99
- 2.4.9.12. Breakpoint 100-108
- 2.4.9.13. Breakpoint 109-117
- 2.4.9.14. Breakpoint 118-120
- 2.5. AIFB1
- 2.6. AIFB2
- 2.7. Measured Values
- 2.8. Filtering
- 3. Diagnostics
- 4. Service
- 5. Communication
- 6. Security
- 7. Language
- Appendix A: Alphabetical Parameter List
- Appendix B: Troubleshooting
- Appendix C: Maintenance
- Appendix D: Technical Reference
- Principles of Operation
- Echo Processing
- Measurement Response
- Damping
- Loss of Echo (LOE)
- Temperature derating curve
- Appendix E: PROFIBUS PA Profile Structure
- Appendix F: Communications via PROFIBUS PA
- Appendix G: Firmware Revision History
- Glossary
- Index
- LCD menu structure
Page 82 SITRANS LR560 (PROFIBUS PA) – OPERATING INSTRUCTIONS 7ML19985LT01
mmmmm
Parameters
2.8.3. Average amount
The fraction of the old shot data that is kept for averaging purposes. A higher
value will give a smoother profile at the expense of a slower echo profile
response.
3. Diagnostics
3.1. Echo Profile
To request a profile via SIMATIC PDM:
Open the menu Device – Echo Profile Utilities. (See
Echo profile on page 46
for more
detail.)
To request a profile via the handheld programmer:
Navigate to Echo Profile (3.1.) and press RIGHT arrow. (See
Requesting an Echo
Profile on page 37
for more details.)
3.2. Fault Reset
Clears the following faults:
To clear a fault using the handheld programmer:
• Enter the fault code number then press RIGHT arrow.
Values
0.0 to 1.0
Default: 0.75
Note: Selected icon is highlighted.
Fault Code
Description
S3 Device Lifetime Reminder 1 (Maintenance Required)
S4 Device Lifetime Reminder 2 (Maintenance Demanded)
S6 Sensor Lifetime Reminder 1 (Maintenance Required)
S7 Sensor Lifetime Reminder 2 (Maintenance Demanded)
S8 Device Service Reminder 1 (Maintenance Required)
S9 Device Service Reminder 2 (Maintenance Demanded)
S12 Internal Temperature High
S17 Calibration Schedule Reminder 1 (Maintenance Required)
S18 Calibration Schedule Reminder 2 (Maintenance Demanded)
measure
pan left/right - selected/highlighted
distance from flange face to target
algorithm selection (trueFirst echo)
TVT
curve
material
level
confidence
value
zoom in/out
exit
Echo Amplitude (dB)
pan up/down
distance from Low Calibration Point to vertical cross-hair
Measurement Range
(0 to 50 m for example purposes)
exit icon selected /
highlighted
exit icon,
deselected