User's Manual
Table Of Contents
- Safety Notes
- FCC Conformity
- CE Electromagnetic Compatibility (EMC) Conformity
- Industry Canada
- The Manual
- Technical Support
- Abbreviations and Identifications
- SITRANS LR560 Overview
- Specifications
- Installation
- Wiring
- Local Operation
- Operating via SIMATIC PDM
- Functions in SIMATIC PDM
- SIMATIC PDM Version
- Quick Start Wizard via SIMATIC PDM
- Changing parameter settings using SIMATIC PDM
- Operating via FDT (Field Device Tool)
- Parameter Reference
- 1. Quick Start
- 2. Setup
- 2.1. Identification
- 2.2. Device
- 2.3. Sensor
- 2.4. Signal Processing
- 2.4.1. Near Range
- 2.4.2. Far Range
- 2.4.3. Minimum Sensor Value
- 2.4.4. Maximum Sensor Value
- 2.4.5. Echo select
- 2.4.6. Sampling
- 2.4.7. Echo Quality
- 2.4.8. TVT setup
- 2.4.9. TVT shaper
- 2.4.9.1. Breakpoint 1-9
- 2.4.9.2. Breakpoint 10-18
- 2.4.9.3. Breakpoint 19-27
- 2.4.9.4. Breakpoint 28-36
- 2.4.9.5. Breakpoint 37-45
- 2.4.9.6. Breakpoint 46-54
- 2.4.9.7. Breakpoint 55-63
- 2.4.9.8. Breakpoint 64-72
- 2.4.9.9. Breakpoint 73-81
- 2.4.9.10. Breakpoint 82-90
- 2.4.9.11. Breakpoint 91-99
- 2.4.9.12. Breakpoint 100-108
- 2.4.9.13. Breakpoint 109-117
- 2.4.9.14. Breakpoint 118-120
- 2.5. AIFB1
- 2.6. AIFB2
- 2.7. Measured Values
- 2.8. Filtering
- 3. Diagnostics
- 4. Service
- 5. Communication
- 6. Security
- 7. Language
- Appendix A: Alphabetical Parameter List
- Appendix B: Troubleshooting
- Appendix C: Maintenance
- Appendix D: Technical Reference
- Principles of Operation
- Echo Processing
- Measurement Response
- Damping
- Loss of Echo (LOE)
- Temperature derating curve
- Appendix E: PROFIBUS PA Profile Structure
- Appendix F: Communications via PROFIBUS PA
- Appendix G: Firmware Revision History
- Glossary
- Index
- LCD menu structure
7ML19985LT01 SITRANS LR560 (PROFIBUS PA) – OPERATING INSTRUCTIONS Page 81
mmmmm
Parameters
2.5.9.2. Value
User-defined default for the Output Value, if sensor or sensor electronic
fault is detected. Units are defined in Unit (2.5.8.2.).
2.6. AIFB2
See AIFB1 (2.5.): the parameters for AIFB2 are identical.
2.7. Measured Values
Read only. Allows you to view measured values for diagnostic purposes
In SIMATIC PDM, open the menu View – Process Variables.
2.7.1. Main Output
The value for Level/Volume. (PV– Primary Value).
2.7.2. Output, no linearization
The value for Level (SV1 – Secondary Value 1).
2.7.3. Output, no level offset
The value for Distance (SV2 – Secondary Value 2).
2.8. Filtering
2.8.1. Narrow Echo Filter
Filters out echoes of a specific width.
To remove a false echo from the Echo Profile, take its width in mm and multiply
it by 0.013. Enter the result.
For example, to filter out a spike with 500 mm width, enter 6 or 7 (the closest
integer product of 500 x 0.013).
When a value is keyed in, the nearest acceptable value is entered.
2.8.2. Reform Echo
Smooths jagged peaks in the echo profile. Reforms fragmented echoes into one
echo.
Note: Fail-safe Mode (2.5.9.) must be set to Substitute Value before Value
(2.5.9.2.) can be defined.
Values
Range: -999999 to 999999
Default: 0
Values
Range: 0 to 255. Default: 0.
0 = OFF
greater = wider
Values
Range: 0 to 255 samples.
Default: 0 (reset to 10 after a Quick Start has been completed)
0 = OFF
greater = wider
Recommended: 5 to 20 samples. Wider is not recommended.