User's Manual
Table Of Contents
- Safety Notes
- FCC Conformity
- CE Electromagnetic Compatibility (EMC) Conformity
- Industry Canada
- The Manual
- Technical Support
- Abbreviations and Identifications
- SITRANS LR560 Overview
- Specifications
- Installation
- Wiring
- Local Operation
- Operating via SIMATIC PDM
- Functions in SIMATIC PDM
- SIMATIC PDM Version
- Quick Start Wizard via SIMATIC PDM
- Changing parameter settings using SIMATIC PDM
- Operating via FDT (Field Device Tool)
- Parameter Reference
- 1. Quick Start
- 2. Setup
- 2.1. Identification
- 2.2. Device
- 2.3. Sensor
- 2.4. Signal Processing
- 2.4.1. Near Range
- 2.4.2. Far Range
- 2.4.3. Minimum Sensor Value
- 2.4.4. Maximum Sensor Value
- 2.4.5. Echo select
- 2.4.6. Sampling
- 2.4.7. Echo Quality
- 2.4.8. TVT setup
- 2.4.9. TVT shaper
- 2.4.9.1. Breakpoint 1-9
- 2.4.9.2. Breakpoint 10-18
- 2.4.9.3. Breakpoint 19-27
- 2.4.9.4. Breakpoint 28-36
- 2.4.9.5. Breakpoint 37-45
- 2.4.9.6. Breakpoint 46-54
- 2.4.9.7. Breakpoint 55-63
- 2.4.9.8. Breakpoint 64-72
- 2.4.9.9. Breakpoint 73-81
- 2.4.9.10. Breakpoint 82-90
- 2.4.9.11. Breakpoint 91-99
- 2.4.9.12. Breakpoint 100-108
- 2.4.9.13. Breakpoint 109-117
- 2.4.9.14. Breakpoint 118-120
- 2.5. AIFB1
- 2.6. AIFB2
- 2.7. Measured Values
- 2.8. Filtering
- 3. Diagnostics
- 4. Service
- 5. Communication
- 6. Security
- 7. Language
- Appendix A: Alphabetical Parameter List
- Appendix B: Troubleshooting
- Appendix C: Maintenance
- Appendix D: Technical Reference
- Principles of Operation
- Echo Processing
- Measurement Response
- Damping
- Loss of Echo (LOE)
- Temperature derating curve
- Appendix E: PROFIBUS PA Profile Structure
- Appendix F: Communications via PROFIBUS PA
- Appendix G: Firmware Revision History
- Glossary
- Index
- LCD menu structure
7ML19985LT01 SITRANS LR560 (PROFIBUS PA) – OPERATING INSTRUCTIONS Page 75
mmmmm
Parameters
2.4.8. TVT setup
2.4.8.1. Auto False Echo Suppression
Used together with Auto False Echo Suppression Range (2.4.8.2.) to screen
out false echoes in a vessel with known obstructions.A ’learned TVT’ (time
varying threshold) replaces the default TVT over a specified range.
•See
Auto False Echo Suppression (2.4.8.1.) on page 118
for a more
detailed explanation.
• To set via SIMATIC PDM see
Auto False Echo Suppression on page
48
.
• To set via local operation see
AFES (Auto False Echo Suppression)
Wizard 1.2. on page 63
.
2.4.8.2. Auto False Echo Suppression Range
Defines the e ndpoint of the Learned TVT distance. Units are defined in Unit
(2.3.1.). Used in combination with Auto False Echo Suppression (see above).
2.4.8.3. Hover Level
Defines how high the TVT (Time Varying Threshold) is placed above the
noise floor of the echo profile, as a percentage of the difference between
the peak of the largest echo in the profile and the noise floor. (See Before
Auto False Echo Suppression on page 49 for an illustration.
)
When the device is located in the center of the vessel, the TVT hover level
may be lowered to increase the confidence level of the largest echo.
2.4.8.4. Shaper Mode
Enables/disables TVT shaper (2.4.9.).
Note: We recommend setting Auto False Echo Suppression either viaSI-
MATIC PDM or via local operation using the Auto False Echo Suppres-
sion wizard.
Values
Range: 0.00 to105.00 m
Default: 1.00 m
Values
Range: 0 to 100%
Default: 40%
Options
*OFF
ON