7ML19985LT01 SITRANS LR560 (PROFIBUS PA) – OPERATING INSTRUCTIONS Page 67
mmmmm
Parameters
2.3.4. Temperature Unit
Selects the engineering unit to be displayed with the value representing
temperature..
2.3.5. Calibration
2.3.5.1. Low Calibration Pt.
Distance from sensor reference point
1)
to Low Calibration Point. Unit is
defined in Unit (2.3.1.) and displayed on the LCD and in PDM.
2.3.5.2. High Calibration Pt.
Distance from Sensor Reference to High Calibration Point. Unit is defined in
Unit (2.3.1.) and displayed on the LCD and in PDM.
When setting the High Calibration Point value, note that echoes are
ignored within Near Range (2.4.1.)
Options
Degrees C, F, R, or K. Default: Degrees C
Note: We recommend using the Quick Start wizard to configure the device.
1)
The point on the sensor from which measurements are referenced (see
Dimensions
on page 12
.
Values
Range: 0 to 100 m. Default: 100.00 m
Related parameters
Unit (2.3.1.)
Far Range (2.4.2.)
Values
Range: 0 to 100 m. Default: 0.000 m
High Level Point
(default: 100%)
sensor
reference
point
Low Level Point
(default: 0%)
Level
Low
Calibration
Point
High
Calibration
Point
Far
Range
Level Offset
(if used)