7ML19985LT01 SITRANS LR560 (PROFIBUS PA) – OPERATING INSTRUCTIONS Page 65
mmmmm
Parameters
1.6. Copy Firmware from Display
Transfers firmware from the local display interface to a device.
SW DOWNLOAD is displayed at the beginning of the transfer. This is followed first by a
blank screen (for approximately 2 minutes), then by a progress indicator, and then by the
Siemens logo with the LOE icon. When the transfer is complete,the device returns to
Measurement mode.
2. Setup
2.1. Identification
2.1.1. Tag
Text that can be used in any way. A recommended use is as a unique label for
a field device in a plant. Limited to 32 ASCII characters.
2.1.2. Descriptor
Text that can be used in any way. Limited to 32 ASCII characters. No specific
recommended use.
2.1.3. Message
Text that can be used in any way. Limited to 32 ASCII characters. No specific
recommended use.
2.1.4. Installation Date
Date the device was first commissioned (text string, no format restrictions).
2.2. Device
2.2.1. Hardware Revision
Read only. Corresponds to the electronics hardware of the Field Device.
2.2.2. Firmware Revision
Read only. Corresponds to the software or firmware that is embedded in the
Field Device.
2.2.3. Loader Revision
Read only. Corresponds to the software used to update the Field Device.
Note: Do not interrupt power supply during transfer.
Notes:
Default settings in the parameter tables are indicated with an asterisk (*) unless
explicitly stated.
Values shown in the following tables can be entered via the handheld programmer.
Note: SITRANS PDM limits the TAG field to a maximum of 24 characters.
Press RIGHT arrow to Edit.
Press DOWN arrow to select
Start and RIGHT arrow to begin
the transfer.