Page 64 SITRANS LR560 (PROFIBUS PA) – OPERATING INSTRUCTIONS 7ML19985LT01
mmmmm
Parameters
i) Navigate to Echo Profile (3.1.) and
press RIGHT arrow to request a
profile. The false echo is now
screened out and the true echo
selected. With Exit icon selected,
press RIGHT arrow to exit.
j) Press LEFT arrow twice to return
to Measurement mode
1.3. Copy Parameters to Display
Transfers parameter settings from a device to the local display interface.
PARAM UPLOAD is displayed, then the device returns to Measurement mode.
1.4. Copy Parameters from Display
Transfers parameter settings from the local display interface to a device.
PARAM DOWNLOAD is displayed, then the device returns to Measurement mode.
1.5. Copy Firmware to Display
Transfers firmware from a device to the local display interface.
SW UPLOAD is displayed during the transfer, then the device returns to Measurement
mode.
true echo
false echo
See
Connecting SITRANS LR560 on page 23
for instructions on
removing the local display interface.
Press RIGHT arrow to Edit.
Press DOWN arrow to select
Start and RIGHT arrow to begin
the transfer.
Press RIGHT arrow to Edit.
Press DOWN arrow to select
Start and RIGHT arrow to begin
the transfer.
Press RIGHT arrow to Edit.
Press DOWN arrow to select
Start and RIGHT arrow to begin
the transfer.