Simulate Output
Manual (user-defined value)
1) Open the menu Device – Simulation, select function block 1 or 2, and click on the tab
Simulation (Output).
2) Select Manual Mode (from options AUTO, Manual, or Out of Service) and click on
Transfer.
3) Enter simulated value and click on Transfer.
4) After simulation is complete, return to Simulate Output, reselect AUTO mode, and
click on Transfer.
Out-of-Service
In Out of Service mode, an out of service status is associated with the value, telling the
master that the value is invalid. This feature can be used during maintenance.
1) Open the menu Device – Simulation, select function block 1 or 2, and click on the tab
Simulation (Output).
2) Select Out of Service Mode and click on Transfer.
3) After maintenance is complete, return to Simulate Output, reselect AUTO mode, and
click on Transfer.