User's Manual

Table Of Contents
Page 40 SITRANS LR560 (PROFIBUS PA) – OPERATING INSTRUCTIONS 7ML19985LT01
mmmmm
SIMATIC PDM
Configuring a new device
1) Check that you have the most recent EDD, and if necessary update it (see
To install a
new EDD
above).
2) Set Address via handheld programmer (default for PROFIBUS PA is 126). (See Device
Address (5.1.) on page 100, to use SIMATIC PDM.)
In PROGRAM mode, navigate to: Level Meter > Communication (5.) > Device
Address (5.1.).
Press RIGHT arrow twice, to open parameter view and enable Edit mode.
If required, key in a new value and press RIGHT arrow to accept it. The LCD
displays the new value.
Press Mode to return to Measurement mode.
3) Launch SIMATIC Manager and create a new project for LR560.
4) Open the menu Device – Master Reset and click on Factory Defaults.
5) After the reset is complete click on Close, then upload parameters to the PC/PG.
6) Configure the device via the Quick Start wizard.
Set Address
Open the menu Device – Set Address, enter a value for New Address, and click on Assign
Address.
Quick Start Wizard via SIMATIC PDM
The graphic Quick Start Wizard provides an easy step-by-step procedure that configures the
device for a simple application.
Please consult the operating instructions or online help for details on using SIMATIC PDM.
1) If you have not already done so, check that you have the most up-to-date Electronic
Device Description (EDD) for your instrument. (See
Electronic Device Description
(EDD)
on page 39.)
2) Launch SIMATIC Manager and create a new project for LR560. Application Guides
for setting up PROFIBUS PA devices with SIMATIC PDM can be downloaded from
the product page of our website at: www.siemens.com/LR560
.
Notes:
Clicking on Cancel during an upload from device to SIMATIC PDM will result in some
parameters being updated.
Application Guides for setting up PROFIBUS PA devices with SIMATIC PDM can be
downloaded from the product page of our website at: www.siemens.com/LR560
.