User's Manual
Table Of Contents
- Safety Notes
- FCC Conformity
- CE Electromagnetic Compatibility (EMC) Conformity
- Industry Canada
- The Manual
- Technical Support
- Abbreviations and Identifications
- SITRANS LR560 Overview
- Specifications
- Installation
- Wiring
- Local Operation
- Operating via SIMATIC PDM
- Functions in SIMATIC PDM
- SIMATIC PDM Version
- Quick Start Wizard via SIMATIC PDM
- Changing parameter settings using SIMATIC PDM
- Operating via FDT (Field Device Tool)
- Parameter Reference
- 1. Quick Start
- 2. Setup
- 2.1. Identification
- 2.2. Device
- 2.3. Sensor
- 2.4. Signal Processing
- 2.4.1. Near Range
- 2.4.2. Far Range
- 2.4.3. Minimum Sensor Value
- 2.4.4. Maximum Sensor Value
- 2.4.5. Echo select
- 2.4.6. Sampling
- 2.4.7. Echo Quality
- 2.4.8. TVT setup
- 2.4.9. TVT shaper
- 2.4.9.1. Breakpoint 1-9
- 2.4.9.2. Breakpoint 10-18
- 2.4.9.3. Breakpoint 19-27
- 2.4.9.4. Breakpoint 28-36
- 2.4.9.5. Breakpoint 37-45
- 2.4.9.6. Breakpoint 46-54
- 2.4.9.7. Breakpoint 55-63
- 2.4.9.8. Breakpoint 64-72
- 2.4.9.9. Breakpoint 73-81
- 2.4.9.10. Breakpoint 82-90
- 2.4.9.11. Breakpoint 91-99
- 2.4.9.12. Breakpoint 100-108
- 2.4.9.13. Breakpoint 109-117
- 2.4.9.14. Breakpoint 118-120
- 2.5. AIFB1
- 2.6. AIFB2
- 2.7. Measured Values
- 2.8. Filtering
- 3. Diagnostics
- 4. Service
- 5. Communication
- 6. Security
- 7. Language
- Appendix A: Alphabetical Parameter List
- Appendix B: Troubleshooting
- Appendix C: Maintenance
- Appendix D: Technical Reference
- Principles of Operation
- Echo Processing
- Measurement Response
- Damping
- Loss of Echo (LOE)
- Temperature derating curve
- Appendix E: PROFIBUS PA Profile Structure
- Appendix F: Communications via PROFIBUS PA
- Appendix G: Firmware Revision History
- Glossary
- Index
- LCD menu structure
7ML19985LT01 SITRANS LR560 (PROFIBUS PA) – OPERATING INSTRUCTIONS Page 35
mmmmm
Quick Start: local
1. Quick Start
1.1. Quick Start Wizard
a) Point the programmer at the display from a maximum distance of 300 mm (1 ft) and
press RIGHT arrow to activate PROGRAM mode and open menu level 1.
b) Press RIGHT arrow twice, to navigate to menu item 1.1
and open the Quick Start Wizard.
c) At each step, press DOWN arrow to accept default
values and move directly to the next item,
or RIGHT arrow to open Edit mode: the current selection is highlighted.
d) Scroll to desired item and press RIGHT arrow to store the change, then press
DOWN arrow to continue.
e) At any time you can press UP arrow to go back, or LEFT arrow to cancel
and return to Measurement mode.
Vessel
Select vessel construction material
.
• Selecting either STEEL or CONCRETE
does a functional reset (see Master
Reset (4.2.) on page 87).
• Selecting STEEL changes the setting
for Position Detect (2.4.5.2.) to Rising
Edge and for Algorithm (2.4.5.1.) to F.
• Selecting CONCRETE changes the setting for Position Detect (2.4.5.2.) to Rising Edge
and for Algorithm (2.4.5.1.) to ALF.
Response Rate
Use a setting just faster than the maximum vessel filling or vessel emptying rate (whichever
is greater).
Options
* STEEL
CONCRETE
Response Rate Vessel Fill/Empty rate/min Filter Time Constant (2.5.8.1.)
SLOW
0.1 m/min (0.32 ft/min)
10 s
MED
* 1.0 m/min (3.28 ft/min)
10 s
FAST
10.0 m/min (32.8 ft/min)
0 s
Parameter View Edit mode
Sets the reaction speed of the device to
measurement changes in the target range.
Selecting SLOW changes setting for
Average amount (2.8.3.) to 0.9.