Wirng
2. Non-incendive and Dust Ignition Proof wiring (US/Canada)
For power demands see
Temperature De-Rating
on page 123.
Instructions Specific to Hazardous Area
Installations
(Reference European ATEX Directive 94/9/EC,
Annex II, 1.0.6)
The following instructions apply to equipment covered by certificate numbers Sira
09ATEX9356X and Sira 09ATEX4357X:
1) For use and assembly and details of marking/coding, refer to the main instructions.
2) The equipment is certified for use as Category 1D, 1/2D and 2D equipment per
certificate Sira 09ATEX9356X and may be used in hazardous zones 20, 21 and 22. The
equipment is also certified for use as Category 3G equipment per certificate Sira
09ATEX4357X and may be used in hazardous zone 2.
3) This equipment has a maximum surface temperature of 139 °C (in an 80 °C ambient).
Refer to the applicable code of practice for selection of this equipment with respect
to specific dust ignition temperatures.
4) The equipment is certified for use in an ambient temperature range of –40 °C to
80 °C.
5) The equipment has not been assessed as a safety related device (as referred to by
Directive 94/9/EC Annex II, clause 1.5).
6) Installation and inspection of this equipment shall be carried out by suitably trained
and authorized personnel in accordance with the applicable code of practice.
FM/CSA Class 1, Div 2 connection drawing number A5E02795836 can be downloaded from
the product page of our website at: www.siemens.com/LR560 under Support.