Page 24 SITRANS LR560 (PROFIBUS PA) – OPERATING INSTRUCTIONS 7ML19985LT01
mmmmm
Wirng
5) Connect the wires to the terminals as shown (SITRANS LR560 PA is not polarity-
sensitive.)
1)
2)
6) Ground the instrument according to local regulations.
7) Tighten the gland to form a good seal.
8) Replace optional display and device lid.
9) Secure the locking screw before programming and device configuration.
Basic PLC configuration with PROFIBUS PA
1)
May be shipped with the device.
2)
The instrument shield connection is internally connected to the external ground lug.
Notes:
PROFIBUS PA must be terminated at both extreme ends of the cable for it to work
properly.
Please refer to the
PROFIBUS PA User and Installation Guidelines
(order number
2.092), available from www.profibus.com
, for information on installing PROFIBUS
devices.
If a Weidmüller or other current limiting junction box is connected to this device,
please ensure that the current limit is set to 40 mA or higher.
cable gland
1)
(or NPT cable
entry)
cable
shield
instrument
shield
connection
2)
PROFIBUS PA
PROFIBUS DP
DP/PA
coupler
active PLC
PC/laptop
PDM
SITRANS
LR560 PA
SITRANS
LR560 PA
SITRANS
LR560 PA