7ML19985LT01 SITRANS LR560 (PROFIBUS PA) – OPERATING INSTRUCTIONS Page 137
mmmmm
F: Communications PA
Extended Mode Diagnosis
When Condensed Status is disabled Extended Mode Diagnosis will be returned, and the
following codes will be used.
Values of the DIAGNOSIS bit: 0 = not set; 1 = set
Extended Mode Diagnosis
Hex values Byte Bit Description
Indication
class
a)
a)
R indicates the message remains active as long as the reason for the message exists.
A indicates the message will automatically reset after 10 seconds
0x01000000
0
0 Electronics failure R
0x02000000 1 Mechanical failure R
0x04000000 2 Motor Temperature too high R
0x08000000 3 Electronics temperature too high R
0x10000000 4 Memory error R
0x20000000 5 Measurement failure R
0x40000000 6 Device not initialized (no calibration) R
0x80000000 7 Self calibration failed R
0x00010000
1
0 Zero point error (limit position) R
0x00020000 1 Power supply failure (electrical, pneumatic) R
0x00040000 2 Configuration invalid R
0x00080000 3 New startup carried out (Warm Start) A
0x00100000 4 Restart carried out (Cold Start) A
0x00200000 5 Maintenance required R
0x00400000 6 Characterization invalid R
0x00800000 7
Set to 1 (one), if the Ident_Number of the running
cyclic data transfer and the value of Physical Block
IDENT__NUMBER_SELECTOR parameter are
different.
R
2 0 to 7 Reserved for use within the PNO
3
0 to 6 Reserved for use within the PNO
0x00000080 7 More diagnosis information is available