User's Manual
Table Of Contents
- Safety Notes
- FCC Conformity
- CE Electromagnetic Compatibility (EMC) Conformity
- Industry Canada
- The Manual
- Technical Support
- Abbreviations and Identifications
- SITRANS LR560 Overview
- Specifications
- Installation
- Wiring
- Local Operation
- Operating via SIMATIC PDM
- Functions in SIMATIC PDM
- SIMATIC PDM Version
- Quick Start Wizard via SIMATIC PDM
- Changing parameter settings using SIMATIC PDM
- Operating via FDT (Field Device Tool)
- Parameter Reference
- 1. Quick Start
- 2. Setup
- 2.1. Identification
- 2.2. Device
- 2.3. Sensor
- 2.4. Signal Processing
- 2.4.1. Near Range
- 2.4.2. Far Range
- 2.4.3. Minimum Sensor Value
- 2.4.4. Maximum Sensor Value
- 2.4.5. Echo select
- 2.4.6. Sampling
- 2.4.7. Echo Quality
- 2.4.8. TVT setup
- 2.4.9. TVT shaper
- 2.4.9.1. Breakpoint 1-9
- 2.4.9.2. Breakpoint 10-18
- 2.4.9.3. Breakpoint 19-27
- 2.4.9.4. Breakpoint 28-36
- 2.4.9.5. Breakpoint 37-45
- 2.4.9.6. Breakpoint 46-54
- 2.4.9.7. Breakpoint 55-63
- 2.4.9.8. Breakpoint 64-72
- 2.4.9.9. Breakpoint 73-81
- 2.4.9.10. Breakpoint 82-90
- 2.4.9.11. Breakpoint 91-99
- 2.4.9.12. Breakpoint 100-108
- 2.4.9.13. Breakpoint 109-117
- 2.4.9.14. Breakpoint 118-120
- 2.5. AIFB1
- 2.6. AIFB2
- 2.7. Measured Values
- 2.8. Filtering
- 3. Diagnostics
- 4. Service
- 5. Communication
- 6. Security
- 7. Language
- Appendix A: Alphabetical Parameter List
- Appendix B: Troubleshooting
- Appendix C: Maintenance
- Appendix D: Technical Reference
- Principles of Operation
- Echo Processing
- Measurement Response
- Damping
- Loss of Echo (LOE)
- Temperature derating curve
- Appendix E: PROFIBUS PA Profile Structure
- Appendix F: Communications via PROFIBUS PA
- Appendix G: Firmware Revision History
- Glossary
- Index
- LCD menu structure
7ML19985LT01 SITRANS LR560 (PROFIBUS PA) – OPERATING INSTRUCTIONS Page 113
mmmmm
B: Troubleshooting
Display shows
S: 0 LOE
antenna malfunction:
• temperature too high
• physical damage
• check temperature in Maximum
Value (3.4.2.)
•relocate
Reading does not
change, but the level
does
SITRANS LR560 processing
wrong echo, i.e. vessel
wall, or structural member
• re-locate SITRANS LR560
• check nozzle for internal burrs or
welds
• rotate instrument 90°
•use Auto False Echo Suppression
(2.4.8.1.) if necessary: see
Auto False
Echo Suppression (2.4.8.1.)
on page
118
Measurement is
consistently off by a
constant amount
• setting for Low Calibra-
tion Pt. not correct
• setting for Sensor Offset
not correct
• check distance from sensor refer-
ence point to Low Calibration Pt.
(2.3.5.1.)
•check Sensor Offset (2.3.5.3.)
Screen blank
power error • check nameplate rating against volt-
age supply
• check power wiring or source
Reading erratic echo confidence weak • refer to Confidence (2.4.7.1.)
•useAuto False Echo Suppression
(2.4.8.1.) and Auto False Echo Sup-
pression Range (2.4.8.2.)
material filling • re-locate SITRANS LR560
Reading response
slow
Fill Rate/Min (2.3.6.2.)
setting is incorrect
• increase measurement response if
possible
Reads correctly but
occasionally reads
high when vessel is
not full
• detecting close range
echo
• build up near top of ves-
sel or nozzle
• nozzle problem
• Use the air purge feature to clean the
antenna
•use Auto False Echo Suppression
(2.4.8.1.) and Auto False Echo Sup-
pression Range (2.4.8.2.)
Level reading lower
than material level
• material is within Near
Range zone
• multiple echoes pro-
cessed
• decrease Near Range (2.4.1.): mini-
mum value depends on antenna type
• raise SITRANS LR560
• ensure Algorithm (2.4.5.1.) is set to tF
(trueFirst echo)
Operation Troubleshooting (cont’d)
Symptom Cause Action