B: Troubleshooting
Operation Troubleshooting
Operating symptoms, probable causes, and resolutions (continued on next page).
S: 41 Transducer temperature too low. Relocate device and/or raise
process temperature enough to
warm device. Inspect for
temperature-related damage and
contact your local Siemens
representative if repair is required.
S:64
to
S:83
Device error.
NOTE: Fault text and icons appear
only on LCD.
Repair required. Contact your local
Siemens representative.
S:94
to
S:108
Device error.
NOTE: Fault text and icons appear
only on LCD.
Repair required. Contact your local
Siemens representative.
Operation Troubleshooting
Symptom Cause Action
Display shows
S: 0 LOE
level or target is out of
range
check specifications
•check Low Calibration Pt. (2.3.5.1.)
increase Confidence (2.4.7.1.)
Display shows
S: 0 LOE
material build-up on
antenna
Use the air purge feature to clean the
antenna
re-locate SITRANS LR560
Display shows
S: 0 LOE
location or aiming:
poor installation
flange not level
Auto False Echo Suppres-
sion may be incorrectly
applied
check to ensure nozzle is vertical
ensure end of antenna protrudes
from end of nozzle.
review
Auto False Echo Suppression
(2.4.8.1.)
on page 118
ensure Auto Suppression Range is
set correctly
General Fault Codes (cont’d)
Code /
Icon
Meaning Corrective Action