User's Manual
Table Of Contents
- Safety Notes
- FCC Conformity
- CE Electromagnetic Compatibility (EMC) Conformity
- Industry Canada
- The Manual
- Technical Support
- Abbreviations and Identifications
- SITRANS LR560 Overview
- Specifications
- Installation
- Wiring
- Local Operation
- Operating via SIMATIC PDM
- Functions in SIMATIC PDM
- SIMATIC PDM Version
- Quick Start Wizard via SIMATIC PDM
- Changing parameter settings using SIMATIC PDM
- Operating via FDT (Field Device Tool)
- Parameter Reference
- 1. Quick Start
- 2. Setup
- 2.1. Identification
- 2.2. Device
- 2.3. Sensor
- 2.4. Signal Processing
- 2.4.1. Near Range
- 2.4.2. Far Range
- 2.4.3. Minimum Sensor Value
- 2.4.4. Maximum Sensor Value
- 2.4.5. Echo select
- 2.4.6. Sampling
- 2.4.7. Echo Quality
- 2.4.8. TVT setup
- 2.4.9. TVT shaper
- 2.4.9.1. Breakpoint 1-9
- 2.4.9.2. Breakpoint 10-18
- 2.4.9.3. Breakpoint 19-27
- 2.4.9.4. Breakpoint 28-36
- 2.4.9.5. Breakpoint 37-45
- 2.4.9.6. Breakpoint 46-54
- 2.4.9.7. Breakpoint 55-63
- 2.4.9.8. Breakpoint 64-72
- 2.4.9.9. Breakpoint 73-81
- 2.4.9.10. Breakpoint 82-90
- 2.4.9.11. Breakpoint 91-99
- 2.4.9.12. Breakpoint 100-108
- 2.4.9.13. Breakpoint 109-117
- 2.4.9.14. Breakpoint 118-120
- 2.5. AIFB1
- 2.6. AIFB2
- 2.7. Measured Values
- 2.8. Filtering
- 3. Diagnostics
- 4. Service
- 5. Communication
- 6. Security
- 7. Language
- Appendix A: Alphabetical Parameter List
- Appendix B: Troubleshooting
- Appendix C: Maintenance
- Appendix D: Technical Reference
- Principles of Operation
- Echo Processing
- Measurement Response
- Damping
- Loss of Echo (LOE)
- Temperature derating curve
- Appendix E: PROFIBUS PA Profile Structure
- Appendix F: Communications via PROFIBUS PA
- Appendix G: Firmware Revision History
- Glossary
- Index
- LCD menu structure
Page 112 SITRANS LR560 (PROFIBUS PA) – OPERATING INSTRUCTIONS 7ML19985LT01
mmmmm
B: Troubleshooting
Operation Troubleshooting
Operating symptoms, probable causes, and resolutions (continued on next page).
S: 41 Transducer temperature too low. Relocate device and/or raise
process temperature enough to
warm device. Inspect for
temperature-related damage and
contact your local Siemens
representative if repair is required.
S:64
to
S:83
Device error.
NOTE: Fault text and icons appear
only on LCD.
Repair required. Contact your local
Siemens representative.
S:94
to
S:108
Device error.
NOTE: Fault text and icons appear
only on LCD.
Repair required. Contact your local
Siemens representative.
Operation Troubleshooting
Symptom Cause Action
Display shows
S: 0 LOE
level or target is out of
range
• check specifications
•check Low Calibration Pt. (2.3.5.1.)
• increase Confidence (2.4.7.1.)
Display shows
S: 0 LOE
material build-up on
antenna
• Use the air purge feature to clean the
antenna
• re-locate SITRANS LR560
Display shows
S: 0 LOE
location or aiming:
• poor installation
• flange not level
• Auto False Echo Suppres-
sion may be incorrectly
applied
• check to ensure nozzle is vertical
• ensure end of antenna protrudes
from end of nozzle.
• review
Auto False Echo Suppression
(2.4.8.1.)
on page 118
• ensure Auto Suppression Range is
set correctly
General Fault Codes (cont’d)
Code /
Icon
Meaning Corrective Action