Page 100 SITRANS LR560 (PROFIBUS PA) – OPERATING INSTRUCTIONS 7ML19985LT01
mmmmm
Parameters
4.10.8. Acknowledge Status
Indicates which level of maintenance reminder has been acknowledged.
In SIMATIC PDM, open the menu View – Device Diagnostics, select Device
Status, click on the Maintenance tab, and check the Calibration Schedule
Status window.
4.10.9. Acknowledge
Acknowledges the current maintenance reminder.
To acknowledge a reminder via SIMATIC PDM:
a) Open the menu View – Device Diagnostics, select Device Status, and click
on the Maintenance tab.
b) In the Calibration Schedule Status section click on Acknowledge
Warnings.
To acknowledge a reminder via the handheld programmer:
a) Press RIGHT arrow twice to open parameter view and activate Edit
Mode.
b) Press RIGHT arrow to acknowledge the reminder.
5. Communication
5.1. Device Address
Sets the unique address of the device on the network (also called PROFIBUS
address).
To reset Device Address via SIMATIC PDM:
See
Set Address on page 40
.
To change Device Address via the handheld programmer:
See
Device Address on page 37
for details.
Note: Default settings in the parameter tables are indicated with an asterisk (*)
unless explicitly stated.
Note: The address can be changed and locked from a remote master. See
PROFI-
BUS address on page 130
for details on disabling the address lock and Master
Reset (4.2.) on page 87 to reset Device Address to 126.
Values
0 - 126. Default: 126