2.3.4. Loss of Echo (LOE) Timer
Sets the time to elapse since the last valid reading, before a fault code is
reported.
2.3.5. Calibration
2.3.5.1. Low Calibration Point
Distance from sensor reference point
1)
to Low Calibration Point
(corresponding to Low Level Point). Unit is defined in Unit (2.3.1.)
2.3.5.2. High Calibration Point
Distance from sensor reference point
1)
to High Calibration Point
(corresponding to High Level Point). Unit is defined in Unit (2.3.1.).
2.3.5.3. Sensor Offset
A constant offset (negative or positive) that can be added to the sensor
value
2)
to compensate if the sensor reference point has shifted. (For
example, this could result from adding a thicker gasket or reducing the
standoff/nozzle height.) The units are defined in Unit (2.3.1.).
For more details see How the LTB works: in the manual, Foundation
Fieldbus for Level instruments (7ML19985MP01).
Note: See
Loss of Echo (LOE) Timer (2.3.4.)
on page 145 for more detail.
Values
Range: 0 to 720 s
Default: 100.000 s
1)
The point on the sensor from which measurements are referenced (see
SITRANS
LR560 with stainless steel universal flat flange
on page 12 and
SITRANS LR560 with
3" Aimer Flange
on page 13).
Values
Range: 0.000 to 40.000 m or 0.000 to 100.000 m.
Default: 100.00 m
Related
parameters
Unit (2.3.1.)
Far Range (2.4.2.)
Values
Range: 0.000 to 40.000 m or 0.000 to 100.000 m.
Default: 100.00 m
2)
See Minimum Sensor Value (2.4.3.) for an illustration.
Values Range: -999999 to 999999 m. Default: 0.00 m
Related
parameters
Unit (2.3.1.)