User's Manual

Table Of Contents
7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 89
mmmmm
Parameters
1.6. Copy Firmware from Display
Transfers firmware from the local display interface to a device.
SW DOWNLOAD is displayed at the beginning of the transfer. This is followed first by
a blank screen (for approximately 2 minutes), then by a progress indicator, and then
by the Siemens logo with the LOE icon. When the transfer is complete,the device
returns to Measurement mode.
2. Setup
2.1. Identification
2.1.1. Tag
Read only. Text that can be used in any way. A recommended use is as a unique
label for a field device in a plant. Limited to 32 ASCII characters.
To access this parameter via AMS Device Manager see Identification under
Identification (RESOURCE) on page 61
.
2.1.2. Descriptor
Read only. Text that can be used in any way. Limited to 32 ASCII characters. No
specific recommended use.
To access this parameter via AMS Device Manager see Identification under
Identification (RESOURCE)
on page 61.
2.1.3. Message
Read only. Text that can be used in any way. Limited to 32 ASCII characters. No
specific recommended use.
To access this parameter via AMS Device Manager see Identification under
Identification (RESOURCE) on page 61
.
2.1.4. Installation date
Read only locally; can be written remotely. The date the device is first
commissioned. (Local display format: YY-MM-DD hh:mm:ss)
Notes:
See
Local Operation
on page 30 or
Operating via AMS Device Manager
on page 41
for instructions.
Default settings in the parameter tables are indicated with an asterisk (*) unless
explicitly stated.
Values shown in the following tables can be entered via the handheld programmer
or local control buttons.
Press RIGHT arrow to Edit.
Press DOWN arrow to select
Start and RIGHT arrow to begin
the transfer.