Page 86 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01
mmmmm
Parameters
Parameter Reference
Parameters are identified by name and organized into function groups. See
LCD menu
structure
on page 155 for a chart.
Parameters noted as
Read Only
in this section of the manual cannot be written via the
local user interface, however they may be accessible via other tools. For those
accessible via AMS Device Manager, directions are shown in the section
Operating via
AMS Device Manager
on the pages referenced.
1. Quick Start
Wizards provide step-by step procedures to configure the device, filter out false echoes,
and upload and download parameters and firmware to the optional display for easy
configuration of multiple LR560s.
Press RIGHT arrow twice to open the Wizards menu. Select a wizard, press RIGHT
arrow to open the first step, and follow the instructions.
1.1. Quick Start Wizard
The Quick Start wizard provides an easy step-by-step procedure to configure the
device for a simple application.
•See
Quick Start Wizard via the LDI push buttons on page 36
.
•See
Quick Start Wizard via the handheld programmer on page 36
.
•See
Quick Start Wizard via AMS Device Manager on page 46
.
Notes:
Most parameters are common to both local and remote operation, and are listed below.
For a complete list of AMS parameters, see
AMS Menu Structure
on page 75.
Default settings in the parameter tables are indicated with an asterisk (*) unless
explicitly stated.
To enter Program mode using the device buttons, press . Press to return to
Measurement mode. Do not use the handheld programmer or local control buttons at the
same time as AMS Device Manager, or erratic operation may result.
For Quick Access to parameters via the handheld programmer, press Home , then
enter the menu number, for example:
2.3.5.
In Navigation mode, ARROW keys navigate the menu in the direction of
the arrow.
Press RIGHT Arrow to open Edit Mode, or to save a modification.