User's Manual

Table Of Contents
7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 135
mmmmm
B: Troubleshooting
Reading does not
change, but the level
does
SITRANS LR560 process-
ing wrong echo, i.e. vessel
wall, or structural member
re-locate SITRANS LR560
check nozzle for internal burrs or
welds
•use Auto False Echo Suppression
(2.4.8.1.) if necessary: see Auto False
Echo Suppression (2.4.8.1.) on page
100
Measurement is con-
sistently off by a con-
stant amount
setting for Low
Calibration Point (2.3.5.1.)
not correct
setting for Sensor Offset
(2.3.5.3.) not correct
check distance from sensor
reference point to Low Calibration
Point (2.3.5.1.)
•check Sensor Offset (2.3.5.3.)
Screen blank
Power error check nameplate rating against
voltage supply
check power wiring or source
Reading erratic Echo confidence weak refer to Confidence (2.4.7.1.)
•use Auto False Echo Suppression
(2.4.8.1.) and Auto False Echo
Suppression Range (2.4.8.2.)
use foam deflector or stillpipe
Material filling re-locate SITRANS LR560
Reading response
slow
Fill Rate/Min (2.3.6.2.) set-
ting is incorrect
increase measurement response if
possible
Reads correctly but
occasionally reads
high when vessel is
not full
detecting close range
echo
build up near top of
vessel or nozzle
nozzle problem
use the air purge feature to clean the
antenna
•use Auto False Echo Suppression
(2.4.8.1.) and Auto False Echo
Suppression Range (2.4.8.2.)
Level reading lower
than material level
material is within Near
Range zone
multiple echoes
processed
decrease Near Range (2.4.1.):
minimum value depends on antenna
type
raise SITRANS LR560
ensure Algorithm (2.4.5.1.) is set to tF
(trueFirst echo)
vessel near empty and
low dK material
•set Position Detect (2.4.5.2.) to Hybrid
check the setting for CLEF Range
(2.4.5.4.)
Operation Troubleshooting (cont’d)
Symptom Cause Action