7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 131
mmmmm
B: Troubleshooting
S: 3 Device is nearing its lifetime limit as
defined in Remaining Lifetime (4.2.3.)
and has triggered Reminder 1
(Required) (4.2.5.).
Replacement is recommended.
S: 4 Device is nearing its lifetime limit as
defined in Remaining Lifetime (4.2.3.)
and has triggered Reminder 2
(Demanded) (4.2.6.).
Replacement is recommended.
S: 6 Sensor is nearing its lifetime limit as
defined in Remaining Lifetime (4.3.3.)
and has triggered Reminder 1
(Required) (4.3.5.).
Replacement is recommended.
S: 7 Sensor is nearing its lifetime limit as
defined in
4.3.3.Remaining Lifetime
and
has triggered a Maintenance
Demanded reminder
(4.3.6.)
.
Replacement is recommended.
S: 8 Service interval as defined in
4.4.1.
has
expired and has triggered a Mainte-
nance Required reminder
(4.4.5.)
.
Perform service.
S: 9 Service interval as defined in
4.4.1.
has
expired and has triggered a Mainte-
nance Demanded reminder
(4.4.6.)
.
Perform service.
S: 10
Input parameters Low Calibration Point
(2.3.5.1.) and High Calibration Point
(2.3.5.2.) are the same.
Check calibration settings of
device.
Ensure settings for High Calibration
Point and Low Calibration Point are
different.
S: 11 Internal temperature sensor failure. Repair required: contact your local
Siemens representative.
General Fault Codes (cont’d)
Code
/Icon
Meaning Corrective Action