7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 129
mmmmm
B: Troubleshooting
If you continue to experience problems, go to our website at:
http://www.siemens.com/LR560
, and check the FAQs for SITRANS LR560, or contact
your Siemens Milltronics representative.
Device Status Icons
Not able to change parame-
ters, such as low calibration
point
Ensure block is set to Out of Service (O/S)
Icon
Priority
Level
Meaning
1 Maintenance alarm
Measurement values are not valid
2 Maintenance warning: maintenance demanded immediately
Measured signal still valid
3 Maintenance required
Measured signal still valid
1 Process value has reached an alarm limit
2 Process value has reached a warning limit
3 Process value has reached a tolerance limit
1 Configuration error
Device will not work because one or more parameters/components
is incorrectly configured
2 Configuration warning
Device can work but one or more parameters/components is
incorrectly configured
3 Configuration changed
Device parameterization not consistent with parameterization in
project. Look for info text.
1 Manual operation (local override)
Communication is good; device is in manual mode.
Symptom Corrective action (contd)