Page 104 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01
mmmmm
Parameters
2.5.3. Channel
Used to select the Transducer Block output. See the manual, Foundation
Fieldbus for Level instruments (7ML19985MP01) for more detail.
2.5.4. Input Scaling
Input scaling should match the XD_scale from the Level Transducer Block. See
the manual
Foundation Fieldbus for Level instruments (7ML19985MP01)
for
more detail.
2.5.4.1. Lower Value
Defines the operational lower range value of the input value (Process Value
Scale) in Level Units. Process Value Scale normalizes the input value to a
customer-defined range.
2.5.4.2. Upper Value
Defines the operational upper range value of the input value (Process
Value Scale) in Level Units. Process Value Scale normalizes the input value
to a customer-defined range.
Options Reference Point
* Level (SV1 - Secondary Value 1) Low Calibration Point
Distance (SV2 - Secondary Value 2) sensor reference point
Values
Range: -999999 to 999999
Default: 0 %
Values
Range: -999999 to 999999
Default: 100 %
Low Calibration Point
(process empty level)
Level (SV1)
Distance (SV2)
sensor reference point
1)
High Calibration
Point
(process full level)
Process Value Scale Input
(typically 0 to 100%)
Output Scale
Provides Output values
(Out) to AIFB 1 or AIFB 2