7ML19985KB01 SITRANS LR560 (mA/HART) – INSTRUCTION MANUAL Page 85
mmmmm
Parameters
2.6. Analog Output Scaling
2.6.1. Current Output Function
Can be set to either Level, Space, or Distance.
To view the mA reading in the secondary region of the LCD, press
on the
handheld programmer.
To modify Current Output Function via SIMATIC PDM:
• Open the menu Device – Select Analog Output.
Notes:
• Level, space, and distance have different reference points.
• Use caution when changing Current Output Function while the device is
connected to a HART network. Current Output Function controls the
primary value. Changes to Current Output Function will update the mA
Setpoints.
• Current Output Function also affects the secondary, tertiary and
quaternary variables in a HART network.
Options Reference point Description
Level Low Calibration Point measured as a percentage of the
difference between High Calibration
Point and Low Calibration Point
Space High Calibration Point
*Distance sensor reference point
measured as a percentage of Low
Calibration Point
Related
Parameters
Units (2.2.1.)
4 mA Setpoint (2.6.2.)/20 mA Setpoint (2.6.3.)
Low Calibration Pt. (2.3.1.)/High Calibration Pt. (2.3.2.)
sensor
ref.
pt.
low
cal.
pt.
high
cal.
pt.
level
space
distance
20 mA
100%
4 mA
0%
4 mA
0%
20 mA
100%
20 mA
100%
4 mA
0%