7ML19985KB01 SITRANS LR560 (mA/HART) – INSTRUCTION MANUAL Page 83
mmmmm
Parameters
2.4.2. Fill Rate/Min
Defines the maximum rate at which the reported sensor value
1)
is allowed to
increase. Allows you to adjust the SITRANS LR560 response to increases in the
actual material level. Fill Rate is automatically updated whenever Response
Rate is altered.
Enter a value slightly greater than the maximum vessel-filling rate, in units per
minute.
2.4.3. Empty Rate/Min
Defines the maximum rate at which the reported sensor value
1)
is allowed to
decrease. Adjusts the SITRANS LR560 response to decreases in the actual
material level. Empty Rate is automatically updated whenever Response Rate
(2.4.1.) is altered.
Enter a value slightly greater than the vessel’s maximum emptying rate, in units
per minute.
1)
The value produced by the echo processing which represents the distance from sen-
sor reference point to the target.
Options
Range: 0 to 999 999 m / min.
(when using AMS, max. value is 99 999 m/min.)
Response Rate (2.4.1.) Fill Rate
Slow 0.1 m/min (0.32 ft/min)
* Medium 1.0 m/min (3.28 ft/min)
Fast 10.0 m/min (32.8 ft/min)
Altered by:
Response Rate (2.4.1.)
Related
parameters
Units (2.2.1.)
Options
Range: 0 to 999 999 m / min.
(when using AMS, max. value is 99 999 m/min.)
Response Rate (2.4.1.) Empty Rate
Slow 0.1 m/min (0.32 ft/min)
* Medium 1.0 m/min (3.28 ft/min)
Fast 10.0 m/min (32.8 ft/min)
Altered by:
Response Rate (2.4.1.)
Related
parameters
Units (2.2.1.)