Page 82 SITRANS LR560 (mA/HART) – INSTRUCTION MANUAL 7ML19985KB01
mmmmm
Parameters
2.3.3. Sensor Offset
A constant offset (negative or positive) that can be added to sensor value
1)
to
compensate if the sensor reference point has shifted. (For example, this could
result from adding a thicker gasket or reducing the standoff/nozzle height.) The
units are defined in
Units (2.2.1.)
2.4. Rate
2.4.1. Response Rate
Sets the reaction speed of the device to measurement changes.
Use a setting just faster than the maximum filling or emptying rate (whichever
is faster).
1)
The value produced by the echo processing which represents the distance from sen-
sor reference point to the target. (see Sensor Mode (2.2.2.) on page 80 for an illustra-
tion).
Values
Range: -100 to 100. Default: 0.00 m
Related
parameters
Units (2.2.1.)
Note: Default settings in the parameter tables are indicated with an asterisk (*)
unless explicitly stated.
Note: Changing Response Rate resets Fill Rate/Min (2.4.2.), Empty Rate/Min
(2.4.3.), and Damping Filter (2.2.3.).
Response Rate
(2.4.1.)
Fill Rate/Min
(2.4.2.)
Empty Rate/Min
(2.4.3.)
Damping Filter
(2.2.3.)
Slow 0.1 m/min (0.32 ft/min) 10 s
* Medium 1.0 m/min (3.28 ft/min) 10 s
Fast 10.0 m/min (32.8 ft/min) 0 s