Page 80 SITRANS LR560 (mA/HART) – INSTRUCTION MANUAL 7ML19985KB01
mmmmm
Parameters
2.1.7. Firmware Revision
Read only. Corresponds to the firmware that is embedded in the SITRANS
LR560.
2.1.8. Loader Revision
Read only. Corresponds to the software used to update the SITRANS LR560.
2.1.9. Menu Timeout
Time menu stays visible before switching back to Measurement view if no key
is pressed.
2.1.10. Date of Manufacture
The date of manufacture of the SITRANS LR560 (dd mm yyyy).
2.2. Sensor
2.2.1. Units
PV (Primary Value) and SV (Secondary Value) units. Used in setting High/Low
Calibration Point, and displayed on LCD and in PDM.
Changing units to % will update the mA setpoints.
2.2.2. Sensor Mode
Values
Range: 15 to 65535 s Default: 120 s
Values
m, cm, mm, ft, in, %
Default: m
Mode Description Reference point
LEVEL
Distance to material surface
Low Calibration Point
(process empty level)
SPACE
High Calibration Point
(process full level)
DISTANCE
*
Sensor Reference Point
sensor
ref.
pt.
low
cal.
pt.
high
cal.
pt.
level
space
distance
20 mA
100%
4 mA
0%
4 mA
0%
20 mA
100%
20 mA
100%
4 mA
0%