Page 58 SITRANS LR560 (mA/HART) – INSTRUCTION MANUAL 7ML19985KB01
mmmmm
AMS Device Manager
3) Click on Apply.
Step 3 – Ranges
1) Click on Step 3.
2) Change units if desired (in meters by default).
3) Set High and Low Calibration points.
4) Set Response Rate.
5) Click on Apply.
Note: Selecting SLOW Response Rate changes setting for Average Amount (2.7.5.3.) to
0.9.