Page 50 SITRANS LR560 (mA/HART) – INSTRUCTION MANUAL 7ML19985KB01
mmmmm
SIMATIC PDM
Master Reset
Factory Defaults
Factory Defaults resets all parameters to the default settings with the following
exceptions:
• Device Address
• Write Protection
• Learned TVT curve
• Auto False Echo Suppression Range
1) Open the menu Device – Master Reset, select OK to perform a reset to Factory
Defaults.
2) After the reset is complete, upload parameters to the PC/PG. (If you are performing a
reset after replacing the device with a different instrument, do not upload
parameters to the PC/PG).
Wear
Reports the number of days the device has been operating, and the number of times it has
been powered up.
Open the menu Device – Wear to view:
• Powered Days
• Power-on Resets
HART Communication
Sets the number of request/response preambles (default 5).
We recommend you do not change this value.
Diagnostics
You can monitor level trends, electronics temperature, and device status.
Process Variables
To compare outputs in real time open the menu View – Process Variables and click on
Overview to see reading (level, space, distance); analog output; device status; and current
electronics temperature.