Page 36 SITRANS LR560 (mA/HART) – INSTRUCTION MANUAL 7ML19985KB01
mmmmm
Quick Start: local
Level application example
The application is a vessel that takes an average 3 hours (180 minutes) to fill and 3 weeks
to empty.
Fill rate = 0.08 m/minute [(Low Cal Pt. minus High Cal Pt.) / fastest of fill or empty time]
= (15.5 m – 1 m) / 180 min.
= 14.5 m /180 min. = 0.08 m/min.
Therefore SLOW response rate (0.1 m/minute) can be selected.
Quick Start Parameter Setting Description
Vessel STEEL Selects vessel construction material.
Response Rate SLOW Resets Fill Rate/ Empty Rate to 0.1 m/minute.
Units M Sensor measurement units.
Operation LEVEL (1) Material level referenced from Low Cal. Point.
Low Calibration Point 15.5 Process empty level.
High Calibration Point 1.0 Process full level.
sensor reference point
Level
Low Cal. Point
High Cal.
Point
15.5 m
1.0 m
LR560