User's Manual

Table Of Contents
7ML19985KB01 SITRANS LR560 (mA/HART) – INSTRUCTION MANUAL Page 33
mmmmm
Quick Start: local
b. Press RIGHT arrow twice to navigate to menu item 1.1
and open the Quick Start Wizard.
c. At each step, press DOWN arrow to accept default
values and move directly to the next item,
or RIGHT arrow to open Edit mode: the current
selection is highlighted.
d. Scroll to desired item and press RIGHT arrow to store the change, then press
DOWN arrow to continue.
e. At any time, you can press UP arrow to go back, or LEFT arrow to cancel
and return to Measurement mode.
Vessel
Select vessel construction material.
Selecting either STEEL or CONCRETE
does a functional reset (see Master
Reset (4.2.) on page 103).
Selecting STEEL changes the setting
for Position Detect (2.7.3.3.) to Rising
Edge and for Algorithm (2.7.3.1.) to F.
Selecting CONCRETE changes the setting for Position Detect (2.7.3.3.) to Rising Edge
and for Algorithm (2.7.3.1.) to ALF.
Response Rate
Use a setting just faster than the maximum vessel filling or vessel emptying rate (whichever
is greater).
Units
Options
* STEEL
CONCRETE
Response Rate
Vessel Fill Rate/Min or Empty Rate/Min
SLOW
0.1 m/min (0.32 ft/min)
MED *
1.0 m/min (3.28 ft/min)
FAST
10.0 m/min (32.8 ft/min)
Parameter View Edit mode
Sets the reaction speed of the device to
measurement changes in the target range.
Selecting SLOW changes setting for
Average Amount (2.7.5.3.) to 0.9.
Sensor measurement units.
Values
m, cm, mm, ft, in.
Default: m