Page 22 SITRANS LR560 (mA/HART) – INSTRUCTION MANUAL 7ML19985KB01
mmmmm
Wiring
Wiring
Power
Connecting
SITRANS LR560
1. Loosen locking screw.
2. Remove LR560 lid.
3. Remove optional display by gently
turning the display a quarter turn
counter-clockwise until it is free.
4. Strip the cable jacket for
approximately 70 mm (2.75") from
the end of the cable, and thread the
wires through the gland
1)
.
WARNINGS:
The DC input terminals shall be supplied from a source providing
electrical isolation between the input and output, in order to meet
the applicable safety requirements of IEC 61010-1.
All field wiring must have insulation suitable for rated voltages.
WARNINGS:
• Check the device label on your instrument, to verify the approval
rating.
• Use appropriate conduit seals to maintain IP or NEMA rating.
•Read
Instructions specific to hazardous area installations
on page 25.
Notes:
• Use twisted pair cable: AWG 22 to 14 (0.34 mm² to 2.5 mm²).
• Separate cables and conduits may be required to conform to standard
instrumentation wiring practices or electrical codes.
1)
If cable is routed through conduit, use only approved suitable-size hubs for
waterproof applications.
1)
2)
3) ¼ turn