Page 8 SITRANS LR560 (mA/HART) – INSTRUCTION MANUAL 7ML19985KB01
mmmmm
Specifications
Memory:
non-volatile EEPROM
no battery required
Interface
Analog output
signal range 4 to 20 mA (±0.02 mA accuracy)
upper limit 20 to 22.6 mA adjustable
lower limit 3.56 to 4 mA adjustable
fail signal 3.56 mA to 22.6 mA; or last value
load Max. 550 Ω @ 24 V DC
Communication: HART
Load 230 to 550 Ω, 230 to 500 Ω when connecting a
coupling module
Max. Line Length
1)
multi-wire: 1500 m (4921 ft)
Protocol HART
2)
, Version 6.0
Configuration
remote Siemens SIMATIC PDM or AMS Device Manager
(PC) or FDT such as PACTWARE
local Siemens infrared handheld programmer, local
control buttons, or HART handheld communicator
Optional removeable graphic LCD, with bar graph representing level
local display interface (LDI)
3)
Mechanical
Process Connections:
universal flat-faced flanges
4)
3"/80 mm, 4"/100 mm, 6"/150 mm
materials stainless steel 316L (1.4404 or 1.4435), or 304
Aimer flanges
4)
3"/80 mm, 4"/100 mm, 6"/150 mm
material polyurethane powder-coated cast aluminum
1)
Max. length depends on wire type. See www.hartcomm.org for more details.
2)
HART® is a registered trademark of HART Communication Foundation.
3)
Display quality will be degraded in temperatures below -20 °C (-4 °F) and above +65 °C (+149 °F).
4)
Universal flange mates with EN 1092-1 (PN16)/ASME B16.5 (150 lb)/JIS 2220 (10K) bolt hole
pattern.