Page 114 SITRANS LR560 (mA/HART) – INSTRUCTION MANUAL 7ML19985KB01
mmmmm
B: Troubleshooting
Appendix B: Troubleshooting
Communication Troubleshooting
1) Check the following:
• There is power at the instrument.
• The LCD shows the relevant data.
• The device can be programmed using the handheld programmer.
• If any fault codes are being displayed, see “General Fault Codes” on page 116
for a detailed list.
2) Verify that the wiring connections are correct.
3) See the table below for specific symptoms.
If you continue to experience problems, go to our website at:
www.siemens.com/sitransLR560
, and check the FAQs for SITRANS LR560, or contact your
Siemens Milltronics representative.
Symptom Corrective action
The device cannot be pro-
grammed via the handheld pro-
grammer.
•Ensure Write Protection (6.1.) on page 110 is set to the
unlock value.
You try to set a SITRANS LR560
parameter via remote communi-
cations but the parameter
remains unchanged.
•Ensure Write Protection (6.1.) on page 110 is set to the
unlock value, then try setting the parameter via the hand-
held programmer.
• Some parameters can be changed only when the device is
not scanning. Try pressing Mode to put the device into
PROGRAM mode.