User's Manual
Table Of Contents
- Table of Contents
- SITRANS LR 460
- Specifications
- Installation
- Wiring
- 4-20 mA Start Up
- Local Operation
- LCD menu structure
- HART Communications
- Remote operation via PROFIBUS PA
- PROFIBUS PA Profile Structure
- Appendix A: Parameter Descriptions
- 1. Identification
- 2. Input
- 3. Output
- 5. Maintenance settings
- 6. Condensed Status Setup
- 6.1. Condensed Status Mode
- 6.1.1. Loss of Echo S0 (Status; Diagnosis)
- 6.1.2. Cable Fault S1 (Status; Diagnosis)
- 6.1.3. No Tech Power S2 (Status; Diagnosis)
- 6.1.4. Device Lifetime Maintenance Required Limit S3 (Status; Diagnosis)
- 6.1.5. Device Lifetime Maintenance Demanded Limit S4 (Status; Diagnosis)
- 6.1.8. Sensor Lifetime Maintenance Demanded Limit S7 (Status; Diagnosis)
- 6.1.9. Device Service Maintenance Required Limit S8 (Status; Diagnosis)
- 6.1.10. Device Service Maintenance Demanded Limit S9 (Status; Diagnosis)
- 6.1.11. LTB Scale S10 (Status; Diagnosis)
- 6.1.12. Internal Temp Sensor S11 (Status; Diagnosis)
- 6.1.13. Internal Temp High S12 (Status; Diagnosis)
- 6.1.16. AIFB2 PV Range S15 (Status; Diagnosis)
- 6.1.19. Calibration Schedule Maintenance Demanded Limit S18 (Status; Diagnosis)
- 6.1.30. Memory EEPROM S29 (Status; Diagnosis)
- 6.1.31. Memory EEPROM Flags S30 (Status; Diagnosis)
- 6.1.32. Memory Flash S31 (Status; Diagnosis)
- 6.1.33. Ident Violation S32 (Status; Diagnosis)
- 6.1.34. Internal Temperature Calibration S33 (Status; Diagnosis)
- 6.1. Condensed Status Mode
- Appendix B: Technical Reference
- Appendix C: Troubleshooting
- Appendix D: Maintenance
- Appendix E: Software Revision History
- Glossary
- Index
7ML19985JM01 SITRANS LR 460 – INSTRUCTION MANUAL Page 70
mmmmm
Parameters
2.5.6. TVT shaper
A breakpoint on the TVT curve, normalized to 0.
2.5.6.1. Shaper A (1-9)
2.5.6.2. Shaper B (10-18)
2.5.6.3. Shaper C (19-27)
2.5.6.4. Shaper D (28-36)
2.5.6.5. Shaper E (37 - 40)
2.5.7. Rate
2.5.7.1. Fill Rate
Defines the maximum rate at which the reported sensor value is allowed
to increase.Allows you to further adjust the LR 460 response to increases
in the actual material level (or an advance to a higher Failsafe Material
Level, P071). Fill Rate is automatically updated whenever Response Rate
is altered.
Enter a value slightly greater than the maximum vessel-filling rate, in
Sensor Units per minute.
Values
Range: 0.0000 to 99999 m / min.
Factory setting: 0.1
Altered by Response Rate
Related Unit (Level)
High Level Point
Handheld programmer Value Meters/Minute
10.1
21
310