User's Manual
Table Of Contents
- Table of Contents
- SITRANS LR 460
- Specifications
- Installation
- Wiring
- 4-20 mA Start Up
- Local Operation
- LCD menu structure
- HART Communications
- Remote operation via PROFIBUS PA
- PROFIBUS PA Profile Structure
- Appendix A: Parameter Descriptions
- 1. Identification
- 2. Input
- 3. Output
- 5. Maintenance settings
- 6. Condensed Status Setup
- 6.1. Condensed Status Mode
- 6.1.1. Loss of Echo S0 (Status; Diagnosis)
- 6.1.2. Cable Fault S1 (Status; Diagnosis)
- 6.1.3. No Tech Power S2 (Status; Diagnosis)
- 6.1.4. Device Lifetime Maintenance Required Limit S3 (Status; Diagnosis)
- 6.1.5. Device Lifetime Maintenance Demanded Limit S4 (Status; Diagnosis)
- 6.1.8. Sensor Lifetime Maintenance Demanded Limit S7 (Status; Diagnosis)
- 6.1.9. Device Service Maintenance Required Limit S8 (Status; Diagnosis)
- 6.1.10. Device Service Maintenance Demanded Limit S9 (Status; Diagnosis)
- 6.1.11. LTB Scale S10 (Status; Diagnosis)
- 6.1.12. Internal Temp Sensor S11 (Status; Diagnosis)
- 6.1.13. Internal Temp High S12 (Status; Diagnosis)
- 6.1.16. AIFB2 PV Range S15 (Status; Diagnosis)
- 6.1.19. Calibration Schedule Maintenance Demanded Limit S18 (Status; Diagnosis)
- 6.1.30. Memory EEPROM S29 (Status; Diagnosis)
- 6.1.31. Memory EEPROM Flags S30 (Status; Diagnosis)
- 6.1.32. Memory Flash S31 (Status; Diagnosis)
- 6.1.33. Ident Violation S32 (Status; Diagnosis)
- 6.1.34. Internal Temperature Calibration S33 (Status; Diagnosis)
- 6.1. Condensed Status Mode
- Appendix B: Technical Reference
- Appendix C: Troubleshooting
- Appendix D: Maintenance
- Appendix E: Software Revision History
- Glossary
- Index
7ML19985JM01 SITRANS LR 460 – INSTRUCTION MANUAL Page 60
mmmmm
Parameters
1.3.3. Hardware Revision
Corresponds to the electronics hardware of the Field Device.
Profile Revision
PROFIBUS PA Profile standard that this device conforms to.
Static Revision No.
The revision level of the static data associated with the Physical Block. The Static
Revision No. is updated whenever a standard profile configuration parameter is
changed.
1.3.4. PROFIBUS Ident Number
Identifies the device on the network. The Ident Number must match that in the
GSD file (the GSD file provides information on the device to the master).
Installation Date
Date on which the device was installed. The user must enter the date.
Local Operation Enable
Enables/disables programming the device via the handheld programmer.When
disabled, the user still has access to the mode control of the two Analog Input
Function Blocks.
1.3.5. Write Locking
Prevents any changes to parameters via PDM or the handheld programmer.
Open the menu Device – Write Locking, and select On or Off.
1.3.6. Language
Selects the language to be used on the LCD.
Values
0
Profile-specific (uses generic device DD and profile GSD for class
B device)
1
Manufacturer-specific (uses SMPI DD and GSD file, which
identifies the LR 460.
Values
2547 (unlock value)
Off (enables programming)
any other value
On (disables programming)
Values
0
English
1
German
2
French
3
Spanish
4
Italian